Table 6.4 Troubleshooting Guide (continued from previous page)
Symptom
Circuit breaker cannot be closed remotely
(can be closed locally)
Circuit breaker cannot be closed locally
(but can be closed remotely)
Circuit breaker does not recharge
electrically but will recharge manually
IB131016EN
Probable Cause
Spring release (closing) coil supply
voltage low or spring release faulty
Secondary contact wiring problem
Latch check switch open
Opening and/or closing
pushbuttons locked
Charging motor supply voltage
absent or too low (< minimum of
range )
Charging motor faulty
For more information visit:
www.Eaton.com
Instruction Book
Effective: November 2017
Corrective Actions
Check power supply voltage;
replace spring release if faulty
Make sure electrical pin and socket
connectors are properly seated in
molded plug. Verify proper wiring
Bad switch or not reset
Check reason for lock
Check charging motor electrical
circuit voltage (check under load)
Replace charging motor assembly