7-2. Operation Data

<Cooling>
Tempeature
condition(°C)
Indoor
Outdoor
42UQV050M
27/19
35/24
42UQV060M
<Heating>
Tempeature
condition(°C)
Indoor
Outdoor
42UQV050M
20/15
7/6
42UQV060M
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 7.5 m
Standard
Model name
pressure
RAS-
P (MPa)
0.9 to 1.1
0.9 to 1.1
Standard
Model name
pressure
RAS-
P (MPa)
2.5 to 2.6
2.6 to 2.8
Heat exchanger
pipe temp.
T1 (°C)
T2 (°C)
11 to 13
40 to 42
11 to 13
41 to 43
Heat exchanger
pipe temp.
T1 (°C)
T2 (°C)
40 to 42
1 to 3
42 to 44
0 to 2
– 21 –
FILE NO. SVM-13035
Indoor
Outdoor
fan mode
fan mode
High
High
Indoor
Outdoor
fan mode
fan mode
High
High
Compressor
revolution
(rps)
67
77
Compressor
revolution
(rps)
79
84