Specifications; Input Power; Output Power; Physical Properties - Motorola GX2-PSDC10D-R Installation And Operation Manual

Table of Contents

Advertisement

Ap pen dix A
S p e c i f i c a t i o n s
Specifications for the GX2-PSDC10D-R are valid over the given operating temperature range. Refer
to the current Motorola BCS product catalog for additional information not provided in this section.
I n p u t P o w e r
DC input voltage
DC current
At -36 V
At -75 V
Power consumption
Efficiency
Fusing
O u t p u t P o w e r
Output voltage
+5.1 VDC range
+12 VDC range
+3.7 VDC range
Output current
+5.1 VDC range
+12 VDC range
+3.7 VDC range
Maximum total output
power
P h y s i c a l P r o p e r t i e s
Dimensions
Weight
Mounting
E n v i r o n m e n t a l
Operating temperature
range
Storage temperature
range
-36 V to -75 V (-48 VDC nominal)
11.7 amps max for fully configured chassis
5.26 amps max for fully configured chassis
385 watts max for fully configured chassis
76% for fully configured chassis
One 15 amp, 250 V, UL listed, slow blow, user replaceable
5.05 to 5.15 VDC nominal
11.88 to 12.12 VDC nominal
3.66 to 3.75 VDC nominal
17.0 amps max for fully configured chassis
12.8 amps max for fully configured chassis
16.0 amps max for fully configured chassis
300 watts max for fully configured chassis
2.2" H x 7.7" W x 11.7" D (5.6 cm x 19.6 cm x 29.7 cm)
8.5 lb (3.9 kg)
GX2-HSG*
-20°C to +60°C (-4° to +140°F)
-40°C to +85°C (-40° to +186°F)
G X 2 - P S D C 1 0 D - R I n s t a l l a t i o n a n d O p e r a t i o n M a n u a l