values taking into consideration as nominal values of the secondary windings
1 Amp and 100 V. If the 5 Amp current inputs are connected applying the
nominal rated current, it will be shown 1 A.
"Channel descriptor" "Channel number ": "Values"
Line description:
Channel descriptor: Analog input
Channel number:
x, where x addresses the analog input channel.
CT (1-5 A) → Rated secondary current related to the current
Values:
input.
CT (0,2 A) → Rated secondary current.
VT (100 V) → Rated secondary voltage (Volt).
Sensor → Voltage output of the sensor (Volt).
Fig. 13.3.-1
Analog inputs commissioning page for the 3CT, 3VT, 1VT, 1CT
module
With sensor inputs, the displayed values are the voltages read by the analog
channels. For example, by using the voltage divider 10.000/1 applying 20 kV
on the sensor, the measurement will show 2 Volt. For the current sensor 80 A/
150 mV, applying 80 Amp on the sensor the measure will be 0.150 Volt.
REF542plus
A051356
43