Error Code - Samsung AM036NXMDCR Service Manual

System air conditioner
Table of Contents

Advertisement

2. Error Code

CODE
E-101
Indoor unit communication error. Indoor unit can not receive any data from outdoor unit.
E-102
Communication error between indoor unit and outdoor unit. Displayed in indoor unit.
E-108
Error due to repeated address setting (When 2 or more devices have same address within the network)
E-109
Incomplete communication error of indoor unit address
E-121
Error on indoor temperature sensor of indoor unit (Short or Open)
E-122
Error on EVA IN sensor of indoor unit (Short or Open)
E-123
Error on EVA OUT sensor of indoor unit (Short or Open)
E-128
EVA IN temperature sensor of indoor unit is detached from EVA IN pipe
E-129
EVA OUT temperature sensor of indoor unit is detached from EVA OUT pipe
E-130
Heat exchanger in/out sensors of indoor unit are detached
E-135
RPM feedback error of indoor unit's cleaning fan
E-149
Error due to AHU master indoor unit sensor setting.
E-151
Error due to opened EEV of indoor unit (2nd detection)
E-152
Error due to closed EEV of indoor unit (2nd detection)
E-153
Error on floating switch of indoor unit (2nd detection)
E-154
RPM feedback error of indoor unit
Mixed operation mode error of indoor unit; When outdoor unit is getting ready to
E-161
operate in cooling (or heating) and some of the indoor unit is trying to operate in heating (or cooling) mode
E-162
EEPROM error of MICOM (Physical problem of parts/circuit)
Indoor unit's remote controller option input is Incorrect or missing.
E-163
Outdo or unit EEPROM data error
E-180
Simultaneous opening of cooling/heating MCU SOL V/V (1st detection)
E-181
Simultaneous opening of cooling/heating MCU SOL V/V (2nd detection)
E-185
Cross wiring error between communication and power cable of indoor unit
E-186
Connection error or problem on SPi
No temperature changes in EVA IN during pipe inspection or changes in temperature is seen in indoor unit with
E-190
wrong address
No temperature changes in EVA OUT during pipe inspection or changes in temperature is seen in indoor unit
E-191
with wrong address
E-198
Error due to disconnected thermal fuse of indoor unit
Communication error between indoor and outdoor units (installation number setting error,
E-201
repeated indoor unit address, indoor unit communication cable error)
Communication error between indoor and outdoor units (Communication error on all indoor unit, outdoor unit
E-202
communication cable error)
E-205
Communication error on all PBA within the outdoor unit C-Box, communication cable error
E-211
When single indoor unit uses 2 MCU ports that are not in series.
E-212
If the rotary switch (on the MCU) for address setting of the indoor unit has 3 or more of the same address
When total number of indoor units assigned to MCU is same as actual number of installed indoor units but there
E-213
is indoor unit that is not installed even though it is assigned on MCU
When number of MCU is not set correctly on the outdoor unit or when two or more MCU was installed some of
E-214
them have the same address
E-215
When two different MCU's have same address value on the rotary switch
E-216
When indoor unit is not installed to a MCU port but the switch on the port is set to On.
hen indoor unit is connected to a MCU port but indoor unit is assigned to a MCU and the switch
E-217
on the port is set to Off
Samsung Electronics
Explanation
Troubleshooting
35