Description; Application Flexibility Outdoor; Application Flexibility Indoor; Typical Indoor Unit - Coleman HL180 Technical Manual

Commercial split-system cooling units four pipe system models hl 15 & hl 20 models ll 15 & ll 20
Table of Contents

Advertisement

DESCRIPTION

Both the outdoor and indoor units are completely piped and
wired at the factory and are shipped ready for immediate
installation. Only the interconnecting liquid and suction lines,
control wiring, and the main power wiring are required to
complete the installation. Every outdoor unit is dehydrated,
evacuated, leak tested and pressure tested at 450 psig
before being pressurized with a holding charge of refrigerant-
22 for shipment and/or storage.
To eliminate the costly cabinet deterioration problems usually
associated with outdoor equipment, all sheet metal parts are
constructed of commercial grade (G90) galvanized steel.
After fabrication, each part is thoroughly cleaned to remove
any grease or dirt from its surfaces. The parts that will be
exposed to the weather are then coated with a desert sand
powder paint to assure a quality finish for many years. This
coating system has passed the 750-hour, salt spray test per
ASTM Standard B117.

APPLICATION FLEXIBILITY OUTDOOR

The outdoor units are lightweight and can be installed on
almost any roof.
Units can be lifted using nylon straps with hooks at the holes
provided in the base rails, or they may be lifted with a forklift
through the slotted openings in the base rails.
A quality appearance and low sound levels make these units
suitable for most ground level locations.
CONDENSER ONLY CAPACITY
Suction
Model HL
Press. &
PSIG ºF
MBH
61.5 35
255
68.5 40
275
240
76
45
296
84
50
319
61.5 35
191
68.5 40
207
180
76
45
224
84
50
241
*Power consumption includes outdoor fans and compressors only.
Unitary Products Group
Temperature of Air on Condenser Coil, ºF
65
75
KW*
MBH
KW*
17.2
243
18.6
17.6
263
19.0
18.1
283
19.5
18.7
305
20.0
12.7
182
13.7
13.0
197
14.0
13.3
214
14.4
13.7
230
14.7

APPLICATION FLEXIBILITY INDOOR

B L O W E R M O T O R
L O C A T I O N
A I R O U T
( S t d . A r r a n g e m e n t )
B L O W E R
S E C T I O N
R E T U R N A I R
D U C T F L A N G E
A I R
I N
F I L T E R S
V E R T I C A L
P O S I T I O N
N O T E : C E R T A I N B L O W E R P O S I T I O N S A R E N O T R E C O M M E N D E D .
B E C A U S E T H E B L O W E R M O T O R S H O U L D N O T B E M O U N T E D
U P S I D E D O W N .
FIGURE 1 : TYPICAL INDOOR UNIT
APPLICATIONS
The indoor units are built in a single cabinet with one conden-
sate drain pan. These units can be installed in either the verti-
cal or horizontal position for maximum flexibility.
NOTE: On vertical applications, the air velocity across the
indoor coil keeps the condensate from dripping off the finned
surface onto the filters:
NOTE: On horizontal applications the unit must be installed
with the condensate drain pan under the entire indoor coil.
NOTE: The Supply Air Plenum and the Return Air Grille
accessories can be used on either arrangement.
NOTE: The Base accessory can only be used on the vertical
arrangement.
85
95
MBH
KW*
MBH
KW*
231
20.1
219
21.9
250
20.6
238
22.4
270
21.1
257
22.9
291
21.6
277
23.4
172
14.9
163
16.2
187
15.2
177
16.5
203
15.5
193
16.9
219
15.9
208
17.3
036-21326-001-C-0202
R E T U R N A I R
D U C T F L A N G E
E V A P O R A T O R
F I L T E R S
C O I L
H O R I Z O N T A L
C O I L
P O S I T I O N
S E C T I O N
A L T E R N A T E A I R
D I S C H A R G E A R R A N G E M E N T S
105
115
MBH KW* MBH KW*
207 23.9 195 26.2
225 24.4 212 26.7
243 24.9 230 27.2
263 25.5 248 27.7
153 17.7 143 19.4
167 18.0 157 19.8
182 18.4 171 20.2
197 18.8 186 20.6
B L O W E R
S E C T I O N
3