Service and troubleshooting
Table 8-30: Mapping errors
Fault
Mapping Error
System continues to re-map
data circuit
Device Type Error
8.48
Possible causes
1.
A discrepancy between the internal map and the devices
installed on the Data Circuit (serial #, personality code, or
device type)
2.
Device ID entered incorrectly into SDU database
3.
More than 124 "T-taps" on a data circuit
4.
Excessive circuit resistance
5.
Excessive circuit capacitance
1.
An intermittent connection causing one or more devices to
loose then re-establish communication with the Signature
controller module
2.
A defective device or detector base
1.
There is a discrepancy between the device type recorded on
the internal map and the device installed on the Data Circuit
EST3 Installation and Service Manual
Need help?
Do you have a question about the EST3 and is the answer not in the manual?