Fig. 4. Economizer with Sylk Bus sensors for enthalpy configuration with a Honeywell MS7305 Direct Coupled Actuator.
W7220 ECONOMIZER CONTROLLER MODULE
2
MS7503
(OPTIONAL COMMUNICATING DCA)
OUTSIDE AIR
TEMP/HUMIDITY (ENTHALPY)
SYLKBUS SENSOR
DISCHARGE AIR
TEMP/HUMIDITY (ENTHALPY)
SYLKBUS SENSOR
24 VAC
1
IN THIS CONFIGURATION, THE MAT IS REQUIRED AND AN OPTIONAL DISCHARGE
AIR TEM/HUMIDITY (ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR
ADVANCED CONTROL AS SHOWN IN THE LOWER LEFT OF THIS FIGURE.
2
IF THE COMMUNICATING ACTUATOR IS USED, IT IS CONNECTED TO THE S-BUS
TERMINALS USING 2-WIRE SYLKBUS
5
JADE™ ECONOMIZER MODULE
ROOF TOP UNIT
O/B
Y1
W1
N
Y2
SD-O/B
OCC
E-GND
AUX
Y2I
Y2O
Y1I
Y1O
C R
THERMOSTAT
WIRING.
G
W2
M32285
62-0331—03