Troubleshooting
Event no. Message
9003
Grid param. locked The current country data set is locked.
9005
Changing grid
param. not
possible
Ensure DC supply
11.4 DC Current after AC-side Disconnection
In spite of the AC side having been disconnected, a current is still detectable in the DC cables with a
current clamp. This is not an error but normal behaviour of the inverter when in operation.
• Always disconnect the inverter on the AC and DC sides (see Section 8.2 "Disconnecting the
Inverter from Voltage Sources" (page 56)).
74
SB25-30TLST-21-IA-en-12
Cause and corrective measures
Corrective measures:
• Enter a valid SMA Grid Guard code for changing the
country data set.
This error can have the following causes:
• The selected rotary switch setting for the language settings
is not programmed.
• The parameters to be changed are protected.
• DC voltage at the DC input is not sufficient to run the main
CPU.
Corrective measures:
• Check the rotary switch setting (see Section 6.5.1
"Checking the Country Standard" (page 45)).
• Enter the SMA Grid Guard code.
• Ensure sufficient DC voltage is available (green LED is
glowing or flashing).