Panasonic AIG707WCL1G2 User Manual page 40

Gt707 series programmable display
Table of Contents

Advertisement

Troubleshooting
Code No.
Content
SD memory card
**1006
recognition error
PLC model unmatch
**1020
error
PLC model
**1021
unsupported error
Password protection
**1022
error
Master memory
**1023
installation error
Program memory
**1024
shortage
General-purpose
**1025
memory shortage
**1027
Remote mode error
**102D
Forced operation error
**1040
**1041
The record area for
logging was
**1042
overwritten.
**1044
SD memory card writing
**1043
error
The record area for
**1045
logging cannot be
reserved in the RAM.
**10A0
ROM write error
Index register value
**1060
error
Start time device value
**1080
error
**E000
Send data overflow
**F000
User's memory error
**F100
OS/System error
4-8
Cause and solution
The SD memory card cannot be recognized. Check the SD memory
card used.
Check if the PLC program for transfer matches the destination PLC.
The selected PLC model is not supported. Confirm the PLC model.
Incorrect passwords were successively input three times . Turn on
the power supply again, and enter the correct password.
The upload protection has been set for the PLC.
The number of digits was changed when setting a new password with
the FP monitor function. Cancel the password setting first to change
the number of digits.
A master memory is installed in the PLC (FP-X). Programs cannot be
transferred to the PLC with the master memory from a SD memory
card.
Program memory shortage in the destination PLC. Decrease the
program size using the PLC tool.
General-purpose memory shortage in the destination PLC.
The PLC (FP2/FP2SH) is set to the RUN mode. Change to the
REMOTE mode or PROG. mode.
Check if a device that cannot be forcibly operated in the PROG.
mode has been forcibly turned on or off.
Check if an SD memory card is inserted.
Data cannot be written into the SD memory card. Check whether the
SD memory card is not write-protected.
The memory of the SD memory card is full. Delete some data in the
SD memory card or prepare a new SD memory card.
The setting to stop writing to SD memory card has been set.
Cancel the writing stop setting.
The setting to stop writing to SD memory card has been set. Cancel
the writing stop setting.
Transfer all data.
The firmware file loaded from the SD card is damaged.
Recreate the file in the SD card.
The device value for index modifier is out of the setting range. Check
the setting value.
The value at the start of the line graph function is out of the setting
range. Check the setting value.
Communication data to PLC overflowed. Some data could not be
sent because of this. Check if the GT communicates with the PLC
properly.
The memory for saving screen data may be damaged. Please contact
your dealer.
It is activated on the OS/system before updating as an error occurred
or the power was cut during the update of the OS/system. Reexecute
the transfer or copy of data from SD to GT performed immediately
before.

Advertisement

Table of Contents
loading

Table of Contents