Daikin D-BACS Design Manual page 359

Buildings air-conditioning control system
Table of Contents

Advertisement

Adaptor
3. Connection of the terminal
Connect between the air conditioner and DTA107A55 shown below.
In case of FD03~05K
DTA107A55
See below for connecting the terminal "M3". (The Output of alarm signal)
About these models, we can only output the alarm signal of indoor fan motor.
Connect the wiring between the terminal "M3" and the terminal "96" of magnetic contactor of indoor fan motor (K1M).
In case of FD06~10K
DTA107A55
See below for connecting the terminal "M3". (The Output of alarm signal)
Use the attached wire harness and change from the wire to it. The wire is connected between K1R(5), K1R(7), K2R(7),
and K3R(5). [ ( )is shown the terminal. ]
Connect the wiring between the terminal "M3" and the solderless splices butt "M3" of the wire assy.
In case of FD15 · 20K
DTA107A55
See below for connecting the terminal "M3". (The Output of alarm signal)
Connect the wiring between the terminal "M1" and the terminal "6" of K4R (magnetic relay).
Connect the wiring between the terminal "M3" and the terminal "4" of K4R (magnetic relay).
In case of UAT06~10K, UAT06~12KA
DTA107A55
See below for connecting the terminal "M3". (The Output of alarm signal)
Use the attached wire harness and change from the wire to it. The wire is connected between K1R(5), K1R(7),
K2R(7), and K3R(6). [ ( )is shown the terminal. ]
Connect the wiring between the terminal "M3" and the solderless splices butt "M3" of the wire assy.
In case of UAT15 · 20K, UAT15~21KA
DTA107A55
See below for connecting the terminal "M3". (The Output of alarm signal)
Connect the wiring between the terminal "M1" and the terminal "6" of K3R (magnetic relay).
Connect the wiring between the terminal "M3" and the terminal "4" of K3R (magnetic relay).
In case of UATY06K
DTA107A55
See below for connecting the terminal "M3". (The Output of alarm signal)
In case of Y1, connect the wiring between the terminal "M1" and the terminal "5" of K2R (magnetic relay).
Connect the wiring between the terminal "M3" and the terminal "3" of K2R (magnetic relay).
In case of Y19, connect the wiring between the terminal "M3" and the terminal "8" of K4R (magnetic relay).
In case of TAL and YAL, use the attached wire harness and change from the wire to it.
The wire is connected between K1R(6), K1R(7), K2R(7), and K3R(6). [ ( ) is shown the terminal. ]
Connect the wiring between the terminal "M3" and the solderless splices butt "M3" of the wire assy.
342
M2
M3
M1
M4
M12
M5
M9
3
A
B
C
M3 M1 M4
M12
M5
M9
M2
A
B
C
D
M3
M1
M4
M12
M13
M5
M9
A
B
C
D
M3
M1
M4
M12
M5
M9
M2
A
B
C
D
P2
P11
P6
P1
M3
M1
M4
M12
M13
M5
M9
A
B
C
D
P2
P11
P8
P6
M3
M1
M4
M7
M5
M9
M10
P2
P17
P6
P10
P13
Connect the wiring between the box of this kit and the
EL. COMPO. BOX ASSY of the indoor unit.
[Refer to the wiring diagram of the indoor unit.]
Connect the wiring between the box of this kit and the
EL. COMPO. BOX ASSY of the indoor unit.
[Refer to the wiring diagram of the indoor unit.]
Connect the wiring between the box of this kit and the
M2
EL. COMPO. BOX ASSY of the indoor unit.
[Refer to the wiring diagram of the indoor unit.]
E
Connect the wiring between the box of this kit and the
EL. COMPO. BOX ASSY of the air conditioner.
K TYPE
[Refer to the wiring diagram of the air conditioner.]
KA TYPE
M2
Connect the wiring between the box of this kit and the
EL. COMPO. BOX ASSY of the air conditioner.
E
K TYPE
[Refer to the wiring diagram of the air conditioner.]
P1
KA TYPE
M12
M2
Connect the wiring between the box of this kit and the
EL. COMPO. BOX ASSY of the air conditioner.
[Refer to the wiring diagram of the air conditioner.]
P11
P1
2.4 <DTA107A55> Central Control Adaptor Kit