Identifying the Failed Cooling Fan Module

To determine which cooling fan module failed, use Dell Storage Manager.
1.
Click the Hardware tab.
2.
In the Hardware tab navigation pane, select and expand the Storage Center.
3.
In the Hardware Alerts area, find the hardware alert that identifies the expansion enclosure with the failed cooling fan module.
Figure 37. Hardware Alert Identifying the Expansion Enclosure with the Failed Cooling Fan
4.
In the Hardware tab navigation pane, expand the expansion enclosure identified in the previous step.
5.
Select Cooling Fans.
The status of each cooling fan module is displayed in the Cooling Fans tab.
6.
Select the failed cooling fan.
The location of the failed cooling fan module is displayed in the Fan View tab.
Figure 38. Rear View of the Expansion Enclosure Showing the Failed Cooling Fan Module

Remove a Cooling Fan Module

Use this procedure to remove a cooling fan module.
Prerequisites
1.
Use SupportAssist to send diagnostic data to Dell Technical Support.
2.
Change the operation mode of the Storage Center to Maintenance.
Replacing SCv360 Expansion Enclosure Components