8 Application of the X-ray regulations

One of the physical properties of vacuum insulations is the
possibility of X-ray emissions when the contact gap is open.
The specified type test performed by the Physikalisch-
Technische Bundesanstalt (PTB) in Brunswick demonstrates
that the local dosage output of 1Sv/h at a distance of 10 cm
from the touchable surface is not exceeded.
The results are as follows:
The use of the vacuum interrupters at rated voltage is
completely safe.
The application of the rated power frequency withstand
voltage specified for the switching devices by VDE 0670
and IEC 62271-100: 2001 is also safe.
Higher voltages than the rated power frequency withstand
voltage or DC test voltage specified in DIN VDE or IEC
standards must not be applied!
Fulfilment of the above requirement with the vacuum
interrupter in the open position is dependent on maintenance
of the specified distance between the contacts (which is
automatically ensured with correct mechanism function and
force transmission).
VD4 Vacuum Circuit-breaker | Application of the X-ray regulations 31