Delivery; Intermediate Storage - ABB VD4 Instruction Manual

Vacuum circuit breaker with embeded poles 36...40,5v, 1250...1500a, 25...31,5ka
Table of Contents

Advertisement

4.4 Delivery

The duties of the consignee on receipt of the switching
devices at site include the following:
Checking the delivery for completeness and freedom
from damage (e.g. moisture and itsadverse effects).
Any short quantities, defects or damage intransit:
Must be precisely documented on the consignment note.
The shipper/carrier is to be notified immediately in
accordance with the liability provisions.
Note:
Always take photographs to document any major damage.

4.5 Intermediate storage

Intermediate storage of the circuit-breaker unit in the switch
position OFF and the storedenergy spring mechanisms
discharged (Indicator DISCHARGED:
Conditions for optimum intermediate storage:
1. Devices with basic packaging or unpacked:
A dry and well ventilated storeroom with climate in
Room temperature which does not fall below-15℃.
Do not remove or damage the packaging.
Unpackaged devices:
Check regularly for any condensation.
2. Devices with seaworthy or similar packaging with internal
protective sheeting:
Store the transport units:
Check the packaging for damage.
).
Check the drying agent:
accordance with GB/T 11022, IEC 60694, DIN VDE 0670.
Are to be loosely covered with protective sheeting.
Sufficient air circulation must be maintained.
protected from the weather,
dry,
safe from damage.
on arrival of the consignment,
subsequently at appropriate intervals.
VD4 Vacuum Circuit-breaker | Dispatch and storage 19