Application; The Protection Of Hv/Mv, Or An Mv/Mv Transformer With Low-Impedance Ef On Both Sides Of Trafo - ABB RET620 Product Manual

Relion 620 series transformer protection and control
Hide thumbs Also See for RET620:
Table of Contents

Advertisement

Transformer Protection and Control
RET620
Product version: 2.0

4. Application

RET620 has been designed to be the main protection for two-
winding power transformers and power generator-transformer
blocks. RET620 also includes an optional voltage regulation
function.
RET620 can be used with either single- or double-busbar
configurations with either one or two breakers, and with
numerous switching device configurations. It supports a
substantial number of both manually and motor-operated
disconnectors and earthing switches, and it is capable of
running large configurations. The number of controllable
devices depends on the number of inputs and outputs left
free from other application needs. The number of available I/
Os can be increased with the RIO600 Remote I/O device.
RET620 offers extensive possibilities to tailor the
configurations to end application requirements. The tool suite
RET620
3U
Uo
Example conf.
3I HV
U
12
Io HV
Io LV
HV
RTD
side
U
12b
LV
3I LV
side
GUID-A758C254-7907-4965-9389-113BCBD77B75 V1 EN
Figure 2.

The protection of HV/MV, or an MV/MV transformer with low-impedance EF on both sides of trafo

10
N
ANSI
IEC
25
SYNC
50L/50NL
ARC
50P/51P
3I>>>
51P/51N
3I/Io
67/67N
3I→/Io→
84M
TPOSM
87T
3dI>T
90V
COLTC
MAP
MAP
49T
3Ith>T
87NH
dIoHi>
87NL
dIoLo>
87NH
dIoHi>
87NL
dIoLo>
for all Relion IEDs is Protection and control IED manager
PCM600, which contains all the necessary tools for
configuring the device, including functionality,
parameterization, the HMI and communication.
RET620 provides both transformer protection and control and
voltage regulator control at the same time. Voltage regulation
capability is targeted for automatic and manual voltage
regulation of power transformers equipped with a motor-
driven on-load tap changer. An automatic voltage regulation
can be applied both with a single transformer as well as with
up to four transformers running in parallel. The IED also
supports both traditional resistor connection-based and
numerically calculated high-impedance earth-fault protection.
To further improve the arc fault protection and minimize the
effects of an arc fault, the 620 series IEDs ordered with the
arc fault protection option can be equipped with an I/O card
featuring high-speed outputs.