ABB VD4 12 Installation And Service Instructions Manual

ABB VD4 12 Installation And Service Instructions Manual

Vd4 series 12 - 24 kv; 630 - 2500 a; 16 - 31.5 ka

Advertisement

Quick Links

VD4
Installation and service instructions
12 ... 24 kV - 630 ... 2500 A - 16 ... 31.5 kA

Advertisement

Table of Contents
loading

Summary of Contents for ABB VD4 12

  • Page 1 Installation and service instructions 12 ... 24 kV - 630 ... 2500 A - 16 ... 31.5 kA...
  • Page 3 Pay special attention to the danger notes indicated in the manual by the following symbol: Responsible behaviour safeguards your own and others’ safety! For any requests, please contact the ABB Assistance Service.
  • Page 4: Table Of Contents

    Index Introduction II. Programme for environmental protection 1. Packing and transport 2. Checking on receipt 3. Storage 4. Handling 5. Description 5.1. General information 5.2. Reference Standards 5.3. Fixed circuit-breaker 5.4. Withdrawable circuit-breaker 5.5. Characteristics of the electrical accessories 6. Instructions for circuit-breaker operation 6.1.
  • Page 5: I. Introduction

    Introduction This publication contains the information needed to install medium voltage VD4 circuit-breakers and put them into service. For correct use of the product, please read it carefully. Like all the apparatus we manufacture, the VD4 circuit-breakers are designed for different installa- tion configurations.
  • Page 6: Packing And Transport

    Packing and transport Should any damage or irregularity be noted in the supply on unpacking, notify ABB (directly or The circuit-breaker is shipped in special pack- through the agent or supplier) as soon as possi- ing, in the open position and with the springs ble and in any case within five days of receipt.
  • Page 7: Handling

    4. Handling During handling, take great care not to stress the insulating parts and the terminals of the cir- Before carrying out any operations, always make cuit-breaker. sure that the operating mechanism springs are discharged and that the apparatus is in the open The apparatus must not be handled by position.
  • Page 8: Description

    The earthing screw is placed in the rear part of the circuit-breaker. For further details, please see the caption to figure 4. 5.3.1. General characteristics of fixed circuit-breakers Circuit-breaker VD4 12 Standards IEC 62271-100 CEI 17-1 (File 1375) Rated voltage...
  • Page 9 Caption 6 Signalling device for closing springs charged/discharged 1 Lever for manual closing spring charging 7 Operation counter 2 Signalling device for circuit-breaker open/closed 8 Terminals 3 Rating plate 9 Earthing screw 4 Opening pushbutton 10 Delivery terminal box 5 Closing pushbutton 11 Cabling connection Fig.
  • Page 10 W = 570 W = 570 W = 700 W = 700 W = 570 W = 700 W = 700 W = 700 VD4 12.06.16 p150 VD4 12.06.20 p150 VD4 12.06.25 p150 31.5 VD4 12.06.32 p150 1250 VD4 12.12.16 p150 1250 VD4 12.12.20 p150...
  • Page 11 5.3.3. Standard fittings for fixed circuit-breakers The basic versions of the fixed circuit-breakers are three-pole and fitted with: – EL type manual operating mechanism – mechanical signalling device for closing springs charged/discharged – mechanical signalling device for circuit-breaker open/closed – closing pushbutton –...
  • Page 12: Withdrawable Circuit-Breaker

    5.4. Withdrawable circuit-breaker The withdrawable circuit-breaker is fitted with The withdrawable circuit-breakers (see fig. 5) are special locks on the front crosspiece, which al- available for UniGear type ZS1 and UniSafe low hooking up into the corresponding couplings switchgear. of the switchgear. They consist of a truck on which the supporting The locks can only be activated by the handles structure of the circuit-breaker is fixed.
  • Page 13 Caption 5 Closing pushbutton 11 Locks for hooking into the fixed part 1 Lever for manually charging the closing 6 Signalling device for closing springs charged/ 12 Handles for activating the locks (11) springs discharged 13 Strikers for activating the contacts placed in 2 Signalling device for circuit-breaker open/ 7 Operation counter the enclosure...
  • Page 14 5.4.2. Types of withdrawable circuit-breakers available for UniGear type ZS1 switchgear VD4/P withdrawable circuit-breaker for UniGear type ZS1 switchgear Rated uninterrupted current (40°C) [A] W = 650 W = 800 W = 1000 W = 1000 W = 800 W = 1000 W = 1000 Circuit-breaker type I = 150...
  • Page 15 VD4/D withdrawable circuit-breaker for UniGear type ZS1 switchgear Rated uninterrupted current (40°C) [A] W = 650 W = 800 W = 1000 W = 1000 W = 800 W = 1000 W = 1000 Circuit-breaker type I = 150 I = 210 I = 275 I = 275 I = 210...
  • Page 16 5.4.4. General characteristics of withdrawable circuit-breakers for UniSafe switchgear Circuit-breaker VD4/P 12 Standards IEC 62271-100 CEI 17-1 (File 1375) Rated voltage Ur [kV] Rated insulation voltage Us [kV] Withstand voltage at 50 Hz Ud (1 min) [kV] Impulse withstand voltage Up [kV] Rated frequency fr [Hz]...
  • Page 17 VD4/P 17 VD4/P 24 17.5 17.5 50-60 50-60 1250 1250 1600 2000 2500 1250 1600 2000 – – – 31.5 31.5 31.5 31.5 31.5 31.5 31.5 – – – – – – – 31.5 31.5 31.5 31.5 31.5 31.5 31.5 –...
  • Page 18 5.4.5. Types of withdrawable circuit-breakers available for UniSafe switchgear VD4/P withdrawable circuit-breaker for UniSafe switchgear Rated uninterrupted current (40°C) [A] W = 600 W = 750 W = 750 W = 1000 W = 800 W = 1000 Circuit-breaker type I = 150 I = 210 I = 210...
  • Page 19 5.4.6. Standard fittings for withdrawable circuit-breakers for UniSafe switchgear The basic versions of the withdrawable circuit-breakers are always three-pole and fitted with: – EL type manual operating mechanism – mechanical signalling device for closing springs charged/discharged – mechanical signalling device for circuit-breaker open/closed –...
  • Page 20: Characteristics Of The Electrical Accessories

    5.5. Characteristics of the electrical Auxiliary contacts of the circuit-breaker accessories 24 ... 220 V AC-DC Rated current: = 10 A Shunt opening release (-M01); Insulation voltage: 2500 V 50 Hz (for 1 min) Additional shunt opening release (-M02); Electrical resistance: 3 mOhm Shunt closing release (-MC) Rated current and breaking capacity...
  • Page 21: Safety Indications

    Instructions for operating Should mechanical operations be car- the circuit-breaker ried out on the circuit-breaker outside the switchgear, be very careful of the 6.1. Safety indications moving parts. The VD4 circuit-breakers guarantee a If the operations are prevented, do not minimum IP2X degree of protection force the mechanical interlocks and when installed in the following condi-...
  • Page 22: Circuit-Breaker Closing And Opening Operations

    6.3. Circuit-breaker closing and opening If the power is cut off during charging, the geared operations motor stops and automatically starts recharging Circuit-breaker operation can be either manual the springs again when the power returns. or electrical (fig. 6 - fig. 7). In any case, it is always possible to complete the recharging operation manually.
  • Page 23: Installation

    – DIN VDE 0141: Earthing systems for installa- For special installation requirements or other tions with rated voltage above 1 kV operating conditions, please contact ABB. – All the accident prevention regulations in force in the relative countries. The areas involved by the passage of power conductors or conductors of aux- 7.2.1.
  • Page 24 7.2.3. Curves of permissible numbers of switching cycles The following graphs show the number of closing-opening cycles (No.) al- lowed, of the vacuum interrupters, according to the breaking capacity (Ia). In = 630 A In = 630 A - 12 kV, 630 A, <...
  • Page 25 In = 2500 A In = 2500 A In = 2000 A In = 2000 A In = 1600 A In = 1600 A High Current High Current - 12-17,5 kV, > 1600 < 25 kA - 12-17,5 kV, > 1600 <...
  • Page 26: Preliminary Operations

    (-MC). The racking-in/-out operations must In ABB trucks, this function is carried out by the always be carried out with the circuit- auxiliary contacts -BT1 and -BT2 which cut of breaker open.
  • Page 27 Check the direction of rotation of the motor-driven Note truck: When the motor fails, the truck can operated – by means of the crank handle (1), manually manually in an emergency. put the withdrawable circuit-breaker in the If the motor fails during a racking in/out central position of the guides (isolated for test/ operation, the truck can be taken to the run end isolated position);...
  • Page 28: Power Circuit Connection Of Fixed Circuit-Breaker

    7.6. Power circuit connections of fixed Assembly procedure circuit-breakers – Put the connections in contact with the circuit- 7.6.1. General recommendations breaker terminals taking care to avoid mechani- – Select the cross-section of the conductors cal stresses (traction / compression) on, for according to the service current and the short- example, the conducting busbars on the ter- circuit current of the installation.
  • Page 29: Earthing

    7.7. Earthing 7.8.1. Fixed circuit-breaker For the fixed version circuit-breaker, carry out Connection of the circuit-breaker auxiliary circuits earthing by means of the special screws marked must be made by means of the terminal box (1) with the relative symbol. Clean and degrease the (fig.
  • Page 30 7.8.2. Withdrawable circuit-breakers The auxiliary circuits of withdrawable circuit- breakers are fully cabled in the factory as far as the connector (fig. 11). For the external connections, refer to the elec- tric wiring diagram of the switchgear. Fig. 11...
  • Page 31: Overall Dimensions

    7.9. Overall dimensions Fixed circuit-breakers 7405 1250 A 31.5 kA 7405 49 28 17.5 kV 1250 A 31.5 kA (*) Interchangeability of fix- ing with the previous se- ries (345 x 400). 7406 1250 A 31.5 kA 7406 17.5 kV 1250 A 31.5 kA (*) Interchangeability of fix-...
  • Page 32 Fixed circuit-breakers 7407 20 20 2xM10 4xM12 1600 A 2000 A 31.5 kA 7407 17.5 kV 1600 A 2000 A 31.5 kA (*) Interchangeability of fix- ing with the previous se- ries (345 x 520). 1600-2000A 7408 20 20 1600 A 2000 A 2500 A 31.5 kA...
  • Page 33 Fixed circuit-breakers 7409 2 x M10 1250 A (*) Interchangeability of fix- ing with the previous se- ries (345 x 520). 7410 2xM10 1250 A (*) Interchangeability of fix- ing with the previous se- ries (345 x 650).
  • Page 34 Fixed circuit-breakers 1600-2000A 7411 2xM10 4xM12 20 20 1600 A 2000 A 7411 2500 A 2500A (*) Interchangeability of fix- ing with the previous se- ries (345 x 650).
  • Page 35 Withdrawable circuit-breakers for UniGear type ZS1 switchgear and UniSafe switchgear VD4/P 630A 1250A 42.5 7412 62.5 36 28 1250 A 31.5 kA VD4/P 7412 17,5 kV 1250 A 31.5 kA VD4/W (1) 7420 62.5 1250 A 31.5 kA VD4/W (1) 7420 17.5 kV 359.5...
  • Page 36 Withdrawable circuit-breakers for UniGear type ZS1 switchgear and UniSafe switchgear VD4/P 62.5 7415 1600 A 2000 A 31.5 kA Width VD4/P 7415- 17.5 kV 359.5 1600 A 2000 A 31.5 kA VD4/P (1) 62.5 7416 1600 A 2000 A 31.5 kA VD4/P (1) 7416 17.5 kV...
  • Page 37 Withdrawable circuit-breakers for UniGear type ZS1 switchgear and UniSafe switchgear VD4/P 62.5 7417 17.5 kV 2500 A 31.5 kA 359.5 VD4/P 630A 1250A 7413 1250 A 31.5 kA 13.5...
  • Page 38 Withdrawable circuit-breakers for UniGear type ZS1 switchgear and UniSafe switchgear VD4/P (1) 630A 1250A 7414 1250 A (1) Only for UniGear type ZS1 switchgear. VD4/P 1600A - 2000A 2500A 7418 1600 A 2000 A 2500 A (2) (2) Only for UniGear ZS1 type switchgear.
  • Page 39: Putting Into Service

    – check tightness of the power connections to All the operations regarding putting into the circuit-breaker terminals; service must be carried out by ABB per- – establish the setting of the primary electronic sonnel or by suitably qualified customer overcurrent release (if provided);...
  • Page 40 ITEM INSPECTED PROCEDURE POSITIVE CHECK Key lock (if provided). Open the circuit-breaker. Neither manual or electrical closing takes place. Turn the key and remove it. Attempt the circuit-breaker closing operation. Put the key back in and turn it 90°. Both electrical and manual closing take place nor- Carry out the closing operation.
  • Page 41: Maintenance

    “Servicing”). lations. It is recommended that ABB service personnel should be called in, at least to check the service performances and for repair work. While the work is in progress, turn the power supply off and put the apparatus under safe con- ditions.
  • Page 42: Servicing

    (for example, Dismantling and replacement of the complete the interlocks). operating mechanism (snap-on box) can only be carried out by ABB personnel or by qualified and specially trained personnel, especially for the 9.2.3. Circuit-breaker pole necessary adjustments.
  • Page 43: Repairs

    (snap-on box) can only be carried Replacement of spare parts and accessories out by ABB personnel or suitably qualified and must only be carried out by ABB personnel or specially trained personnel, especially for the suitably qualified and specially trained person- necessary adjustments.
  • Page 44: Spare Parts And Accessories

    The specific tests carried out at the PTB labora- the spare parts, by ABB personnel or tories (Physikalisch-Technische Bundesanstalt, by suitably qualified customer person- in Brunswick - Germany) show that local emis-...
  • Page 45: List Of Spare Parts

    11.1. List of spare parts – Shunt opening release – Additional shunt opening release – Undervoltage release – Contact for signalling undervoltage release energised/de-energised – Time delay device for undervoltage release – Mechanical override for undervoltage release – Shunt closing release –...
  • Page 46 Notes...
  • Page 48 ABB Trasmissione & Distribuzione S.p.A. ABB Calor Emag Mittelspannung GmbH Unità Operativa Sace T.M.S. Oberhausener Strasse 33 Petzower Strasse 8 Via Friuli, 4 D-40472 Ratingen D-14542 Glindow I-24044 Dalmine Phone: +49(0)2102/12-1230, Fax: +49(0)2102/12-1916 Tel: +39 035 395111 E-mail: calor.info@de.abb.com Fax: +39 035 395874 Internet:http://www.abb.de/calor...

This manual is also suitable for:

Vd4 17Vd4 24

Table of Contents