5.4
You can use terminal X210A.1 in order to supply a safety control device. Only use the
power supply for the device connected to the frequency inverter. Other safety control
devices must not be connected. The maximum output current is 180 mA. The con-
nected device must not have higher current requirements.
6
During operation, the projected and commissioned machine components must not be
changed. If the machine is modified a new acceptance inspection is required.
Check the safety function at regular intervals. The test intervals are to be determined
according to the risk analysis. However, the check should be performed once every
year, at the latest.
7
The acceptance inspection of the safety function is ordered by the manufacturer of
the machine. The inspection (acceptance) shall be performed by a properly qualified
person.
The result of the inspection is to be documented and must be signed by the inspec-
tor. Each safety function must be documented in detail in this report.
The inspections also include the machine documentation, including its safety func-
tions. The safety functions must be checked particularly during the inspection and
documented in the inspection report. Parameter settings shall be attached to the
report. Further documents shall be added, as required, depending on the machine.
Depending on the result of the risk analysis, inspection reports of the regular inspec-
tions shall be issued and signed by the inspector.
16
DC 24 V Power supply by ACU
Requirements to be met in operation
Requirements to be met by acceptance inspection
ACU-STOV1-01SV2-03 en
03/11