Motor Lubrication Screen; Figure 40 - Motor Lubrication Screen - York YK Series Operation Manuals

R-134a cooling only, with optiview control center, for electro-mechanical starter, solid state starter and variable speed drive
Hide thumbs Also See for YK Series:
Table of Contents

Advertisement

FORM 160.54-O1
ISSUE DATE: 9/10/2014

FIGURE 40 - MOTOR LUBRICATION SCREEN

OVERVIEW
(This feature applies to software version C.MLM.01.14.
xxx (and later) or C.OPT.01.14.306 (and later) only)
This feature provides an indication when the compres-
sor motor lubrication is required. The lubrication re-
quirement and notification is based on the operating
hours since last motor lubrication. There are up to three
levels of notification, each indicating an increasing
level of urgency. WARNING – MOTOR BEARING
LUBE SUGGESTED is displayed when the hours ex-
ceed 1000 hours. If there is no response, WARNING –
MOTOR BEARING LUBE REQUIRED is displayed
when the hours exceed 1200 hours. If there is still no
response, a safety shutdown is performed when the
hours exceed 1400 hours and Motor – Lack Of Bearing
Lubrication is displayed. Refer to SECTION 3 - DIS-
PLAY MESSAGES on Page 175 of this manual for de-
tails of these messages.
To provide a record of when a motor lubrication is per-
formed, the Operator enters his/her initials, name or
user ID using the MOTOR LUBE ACKNOWLEDGE
key. The date and time of this entry is automatically
logged as the Date of Last Lubrication and Time of
JOHNSON CONTROLS

MOTOR LUBRICATION SCREEN

SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
Last Lubrication. This also clears any motor lubrica-
tion warning or safety that is in effect and resets the
operating hours since last lubrication to zero.
If equipped with software version C.OPT.01.16.XXX
(or later), this lubrication notification and shutdown
feature can be enabled or disabled based on the cus-
tomer's preference using the AUTO LUBE and SHUT-
DOWN keys.
DISPLAY ONLY
Date of Last Motor Lubrication Warning or
Fault
Displays the date of the last motor lubrication warning
or safety shutdown.
Date of Last Motor Lubrication
Displays the date of the last motor lubrication. This pa-
rameter is automatically recorded when the Operator
enters his/her initials, name or user ID using the MO-
TOR LUBE ACKNOWLEDGE key.
LD10702
115
2

Hide quick links:

Advertisement

Table of Contents
loading