Appendix D : Toshiba Error Code Cross-Reference

Black Pear
Error Code
Error Code
1005
1006
1012
2001
2002
2003
2004
2006
2007
2008
2009
2010
2012
2015
2016
2018
2019
2020
2023
2025
2026
2028
2031
3001
3002
3003
3004
3005
3006
3007
3008
3010
3012
3013
3015
3016
3023
3024
3029
3031
4001
4002
4003
4004
4006
4007
4008
4014
4016
Toshiba
Description
C05
Sending error in TCC-LINK central control device
C06
Receiving error in TCC-LINK central control device
C12
Batch alarm of general-purpose equipment control interface
E01
Communication error between indoor and remote controller
(Detected at remote controller side)
E02
Sending error of remote controller
E03
Communication error between indoor and remote controller
(Detected at indoor side)
E04
Communication circuit error between indoor and outdoor
(Detected at indoor side)
E06
Decrease of No. of indoor units
E07
Communication circuit error between indoor/outdoor
(Detected at outdoor side)
E08
Duplicated indoor addresses
E09
Duplicated master remote controllers
E10
Communication error between indoor P.C.board
E12
Automatic address start error
E15
No indoor automatic address
E16
Capacity over / No. of connected indoor units
E18
Communication error between indoor header and follower units
E19
Outdoor header units quantity error
E20
Other line connected during automatic address
E23
Sending error in communication between outdoor units
E25
Duplicated follower outdoor address
E26
Decrease of No. of connected outdoor units
E28
Follower outdoor unit error
E31
IPDU communication error
F01
Indoor TCJ sensor error
F02
Indoor TC2 sensor error
F03
Indoor TC1 sensor error
F04
TD1 sensor error
F05
TD2 sensor error
F06
TE1 sensor error
F07
TL sensor error
F08
TO sensor error
F10
TA sensor error
F12
TS1 sensor error
F13
TH sensor error
F15
Outdoor temp. sensor misconnection (TE1,TL)
F16
Outdoor pressure sensor misconnection (Pd,Ps)
F23
Ps sensor error
F24
Pd sensor error
F29
Indoor other error
F31
Outdoor EEPROM error
H01
Compressor break down
H02
Magnet switch error / Overcurrent relay operation / Compressor error (lock)
H03
Current detection circuit error
H04
Comp-1 case thermo operation
H06
Low pressure protective operation
H07
Low oil level protection
H08
Oil level temp. sensor error
H14
Comp-2 case thermo operation
H16
Oil level detection circuit error / Magnet switch error / Overcurrent relay error