3. 2 Precaution for inverter mounting to the enclosure

Enclosure design and layout are important points for controlling EMC. Perform
installation by considering the following points.
(1) Use a metal enclosure.
(2) Use EMI gasket or other conductive packing to where the enclosure door touches
the enclosure body.
body is another effective measure.
(3) It is recommended to
or available as an option. When using an option EMC filter, mask the painting or
plate the area of the enclosure where the EMC filter is mounted so that the electrical
connection can be established between the EMC filter and the ground (earth) of the
enclosure. Confirm that the EMC filter is securely fitted to the enclosure surface.
Confirm that the equipment mounting board inside the enclosure is also connected
to the ground (earth).
Mounting enclosure surface
a short thick rectangular wire to connect the door to the
Using
EMI gasket
Enclosure
the inverter with the EMC filter, which is already embedded
use
EMC
Metal enclosure
The part of the enclosure that
the EMI gasket touches
should be conductive.
3 - 2
Mask the painting or
plate the area.