For the same reason stated for Cold Water Starts, it is even more important to provide protection against condensation
from cold inlet water on systems where the return water temperature to the boiler will always be below the acceptable
minimum. Raypak's Cold Water Run system utilizes a variable-speed pump to inject just the right amount of water
from the main system loop into the boiler to maintain the optimum inlet temperature. This approach allows the full
capacity of the boiler to be utilized to meet the system load, while at the same time continuously maintaining the opti-
mum inlet water temperature to prevent condensation.
MIN INLET
TEMP SETTING
START-UP
TEMP
Raypak's Cold Water Run system:
Continuously monitors and adjusts inlet water temperature to prevent condensation
Regulates minimum inlet water temperature regardless of system temperature
Shuts down boiler if the minimum inlet water temperature is not achieved
Protects boiler from constant low return water temperatures with its proprietary self-tuning controller
Utilizes variable-speed injector pump to control boiler loop temperature
Activates alarm if shutdown occurs (option)
Boiler Start-Up Cycle
BLENDED BOILER
INLET TEMP
TIME
COLD WATER RUN
SYSTEM RETURN
A A P P P P L L I I C C A A T T I I O O N N S S
Pool Heating
Low-temperature Industrial Process
Very Low-temperature Return Water
(e.g. convalescent hospital domestic
hot water)