Electrical Requirements - Lochinvar COPPER-FIN II CF401 Designer's Manual

400,000 – 2,070,000 btu/hr
Table of Contents

Advertisement

Lochinvar
Acceptable Water Quality Levels
NOTE:
Maximum Water Hardness = 25 Grains
Incorrect piping
of the cold water
Minimum Water Hardness = 5 Grains
supply to the
Maximum Total Dissolved Solids = 350 PPM
system will result
Range of Acceptable pH = 7.2 to 7.8
in condensate formation
on the
Standard production Lochinvar water heaters
heat exchanger
are designed to operate free of impurity
and operational
build-up in the heat exchanger when
problems. Higher water
properly installed and operated under the
temperatures reduce
specified water quality conditions.
condensate formation.
Refer to drawings in
For installation in areas outside these
Appendix A.
parameters, please consult the factory.
Water Flow Switch
Due to the low water content (between 1
and 6 gallons) of the copper finned tube
heat exchanger, a flow switch is factory
installed as a low water cutoff device on
models CF401 thru CF2071. The flow
switch is installed in the outlet piping from
the water heater and wired in series with the
ignition system safety controls.
NOTE:
When the unit is
In most localities, a flow switch is acceptable
installed in Canada, it
as a low water cutoff device on water
must conform to the
heaters requiring forced circulation. It is
CAE C22.1,
prudent to verify acceptance with the local
Canadian Electrical
code official.
Code, Part 1,
and/or local Electrical
Relief Valve
Codes.
This water heater is supplied with
temperature and pressure relief valve(s)
sized in accordance with ASME Boiler and
Pressure Vessel Code, Section IV "Heating
Boilers."
20
L o c h i n v a r
'
D E S I G N E R
S G U I D E C O P P E R
(TABLE N) – COMMON WATER MANIFOLD
SIZE FOR MULTIPLE WATER HEATER
INSTALLATION
Pipe sizing chart provides minimum pipe size for
common manifold piping to ensure adequate flow.
NUMBER OF
UNITS
CF 401 thru 751
1
2
3
4
5
6
CF 991 thru 2071
1
2
3
4
5
6

ELECTRICAL REQUIREMENTS

(North America)
The appliance is wired for 120 volts.
All wiring between the unit and field
1.
installed devices shall be made of type
T wire [63°F (35°C) rise].
The pump must be wired to run
2.
continuously when unit is firing.
It is recommended that the water heater
3.
and pump be wired on separate circuits
with properly sized breakers.
(TABLE O) – AMP DRAW DATA
MODEL
FAN(S)
CONTROLS
NUMBER
CF401
3.6
2.7
CF501
3.6
2.7
CF651
5.4
3.4
CF751
5.4
3.4
CF991
3.2
7.2
CF1261
3.2
7.2
CF1441
6.7
7.2
CF1801
6.7
7.2
CF2071
6.7
7.2
-
F I N I I W A T E R H E A T E R
COMMON MANIFOLD SIZE
(Min.)
2"
3"
3
1
/
"
2
4"
5"
5"
2
1
/
"
2
4"
4"
5"
6"
6"
PUMP
TOTAL AMPS
w/PUMP
5.0
11.3
5.0
11.3
5.0
13.8
5.0
13.8
5.8
16.3
5.8
16.3
5.8
19.8
5.8
19.8
5.8
19.8