240v ac digital input and output modules (18 pages)
Summary of Contents for Allen-Bradley Flex integra 1793-IB16
Page 1
Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment SERVICE CENTER REPAIRS WE BUY USED EQUIPMENT • FAST SHIPPING AND DELIVERY Experienced engineers and technicians on staff Sell your excess, underutilized, and idle used equipment at our full-service, in-house repair center We also offer credit for buy-backs and trade-ins •...
Installation Instructions FLEX Integra 16 Sink Input Module (Cat. No. 1793-IB16 and -IB16S) Module Installation This module mounts on a DIN rail. It connects to an adapter or another FLEX I/O or Integra module. Note: If using this module with FLEX I/O modules, do not mount between FLEX I/O modules.
Page 3
FLEX Integra 16 Sink Input Module 4. Press down to lock the module on the DIN rail. 30870-M If the module does not lock in place, use a screwdriver of similar device to move the locking tab down, press the module flush with the DIN rail and release the locking tab to lock the module in place.
FLEX Integra 16 Sink Input Module ATTENTION: Do not remove this module under power. Removing this module under power will break the electrical backplane (flexbus) connections. This can cause personal injury or property damage by: • sending an erroneous signal to your system's field devices causing unintended machine motion •...
Page 5
FLEX Integra 16 Sink Input Module Wiring This module is available with 2 styles of terminations: 1793-IB16 - screw-cage and 1793-IB16S - spring-clamp. Refer to the wiring figure below. 1793-IB16 4 5 6 7 9 10 11 12 13 14 15 41816 1793-IB16S 9 10...
FLEX Integra 16 Sink Input Module Wiring Connections Channel Input Power Channel Input Power connect to connect to corresponding corresponding terminal on terminal on row row B +24V dc Power terminals V are internally connected together in the module. 24V dc Common terminals COM are internally connected together in the common module.
FLEX Integra 16 Sink Input Module Indicators 1793-IB16 24 VDC SINK INPUT 9 10 11 12 13 14 15 41812 A = Status indicators - 0 through 15 - shows status of individual inputs B = Insertable label for writing individual input designations Memory Mapping Bit/ 09 08 07 06 05 04 03 02 01 00...
Page 8
FLEX Integra 16 Sink Input Module Setting the Input Delay Time You can select the input delay time (DT) for channels 00 thru 011, and channels 12-15. Select the input delay time by setting the corresponding bits in the output image table (complementary word) for the module. For example, to set a delay time of 4ms for an input module at address rack 1, module group 0, set bits05, 04, 03, 02, 01 and 00 as shown below.
Page 9
FLEX Integra 16 Sink Input Module Approbation d’utilisation dans des C-UL and UL Hazardous Location Approval environnements dangereux par la C-UL and UL La C-UL and UL certifie des produits pour une C-UL and UL certifies products for general use as utilisation générale aussi bien que pour une well as for use in hazardous locations.
Page 10
FLEX Integra 16 Sink Input Module Approbation d’utilisation dans des C-UL and UL Hazardous Location Approval environnements dangereux par la C-UL and UL W@SUDTT@H@IUÃ)ÃSvrÃqryv WARNING: Explosion Hazard • Substitution of components may impair • La substitution de composants peut rendre ce suitability for Class I, Division 2.
Page 11
FLEX Integra 16 Sink Input Module Specifications - 16 Input Module Cat. No. 1793-IB16 and -IB16S Module Type 16 digital input - sinking 1793-IB16 - screw-cage terminations 1793-IB16S - spring-clamp terminations Module Location DIN rail mounting Number of Channels 16 (1 group of 16, nonisolated, sinking) On-state Voltage 10V dc minimum 24V dc nominal...
FLEX Integra 16 Sink Input Module Specifications - 16 Input Module Cat. No. 1793-IB16 and -IB16S Screw Terminal Torque 5-7 lb-in (0.5-0.6Nm) Agency Certification • C-UL Listed (when product is marked) • C-UL Class I, Division 2 Groups A, B, C and D certified •...
Page 14
Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment SERVICE CENTER REPAIRS WE BUY USED EQUIPMENT • FAST SHIPPING AND DELIVERY Experienced engineers and technicians on staff Sell your excess, underutilized, and idle used equipment at our full-service, in-house repair center We also offer credit for buy-backs and trade-ins •...