Table 1A — Physical Data — 38AUD*16-25 Units — 50 Hz SI
UNIT SIZE 38AU
NOMINAL CAPACITY (kW)
OPERATING WEIGHT (kg)
NOVATION™ Coil (Al Tube)
Round Tube/Plate Fin Coil (Cu/Al)
REFRIGERANT TYPE
Operating Charge A/B, Typical (kg)
Shipping Charge A/B (kg)
COMPRESSOR
Qty...Model
Oil Charge (L)
No. Cylinders
Speed (r/s)
CONDENSER FANS
Qty...r/s
Motor Hp NEMA
Diameter (mm)
Nominal Airflow (L/s)
Watts (Total)
CONDENSER COIL (Qty)
Face Area (sq m total)
Rows/Fins per Meter (Fins/m)
Storage Capacity A/B (kg)**
CONTROLS
Pressurestat Settings (kPa)
High Cutout
Cut-in
Low Cutout
Cut-in
PIPING CONNECTIONS (mm ODS)
Qty...Suction
Qty...Liquid
LEGEND
NEMA — National Electrical Manufacturers Association
ODS — Outside Diameter Sweat (socket)
Unit is factory-supplied with partial charge only.
Typical operating charge with 7.62 m of interconnecting piping.
** Storage capacity of condenser coil with coil 80% full of liquid R-410A at 35°C.
D*16
D*25
52.7
70.3
288
409
R-410A
6.4/6.4
9.5/9.5
2.7/2.7
8.6/8.6
Scroll
2...ZP83
2...ZP103
1.7
N/A
N/A
58
3...18
4...18
1
/
4
560
560
3933
5506
810
960
2...NOVATION
2...RTPF
4.6
1...670
2...670
3.0/3.0
9.5/9.5
4347 ± 70
3482 ±138
372 ± 21
807 ± 34
2...34.93
2...34.93
2...12.7
2...12.7
5
3.2
58
1
/
4
4.6

Hide quick links: