Input Req set for VALUE means this WX16 channel reads the OLCT 200's monitored
gas value. If the Input Req menu is set for BATT this WX16 channel reads the battery
voltage from the OLCT 200 with the same Remote ID. To properly display an OLCT
200's battery voltage the WX16 engineering unit range should be 0-5.00 VDC. Even if
this channel reads VALUE from the OLCT 200, the battery voltage is displayed at the
bottom of this WX16 menu as shown in Figure 6-3.
Figure 6-3: WX16 Base Station "Data From" Menu
6.5.2
OLCT 200 AND WX4 BASE STATIONS
FIGURES 6-4 and 6-5 show correct settings for a WX4 base station to receive
data from OLCT 200's.
Figure 6-4
WX4 base stations must have their Communications menus set for Wireless Receiver
mode as shown in Figure 6-4. In Receiver mode the WX4 may have 1-4 channels
configured to receive input data from 1-4 OLCT 200 sensor transmitters.
Channel input type is configured in the ANALOG SETUP menu located within the
Input/Output Setup menus as shown in Figure 6-5. OLCT 200's transmit 200 counts
for 0% and 1000 counts for 100% full scale readings so Input Min/Max menu values
should be 200 & 1000. The Rmt. Xmitter ID menu entry must match the Remote Id
address setting in the OLCT 200 providing data to this WX4 channel. Voltage level of
the 3.6 volt lithium battery in this OLCT 200 is also displayed on this screen. The most
recent A/D Counts value is displayed at bottom of the screen.