Alarm Status Word
(16 bit status word; bit assignment for system status)
CH1_ALM1
CH1_ALM2
CH1_FAULT
CH2_ALAM1
CH2_ALM2
CH2_FAULT
K1_STATUS
K2_STATUS
K3_STATUS
Transmitter Status Word
(16 bit status word; bit assignment for system status)
CHAN_1_ACTIVE
CHAN_2_ACTIVE
SECURE_LEVEL
MARKER Tx LED
K1_FAILSAFE
K2_FAILSAFE
K2_ACK
LOCK
Chan 1 Sensor Life
Chan 2 Sensor Life
(16 bit signed integer ranging from –1 to 100 where -1 indicates Cal Required)
Chan 1 Sensor Temperature 31011
Chan 2 Sensor Temperature 31012
(16 bit integer ranging from 1 to 4095 scaled for –55 to +125 degrees C)
Memory Floating Point:
Note: Returned as 15bit plus sign 2s complement with +/- 5% over/underrange applied. Consider
over/underrange when scaling values to be displayed at the workstation. The following equation
may be used to determine a value for display.
Display Value = MODBUS Value [ (Span Value -Zero Value) 1.1] + {Zero Value - [(Span Value - Zero Value)
.05]}
32767
FP Value Chan 1
FP Value Chan 2
Memory ASCII Strings:
User Info Chan 1
User Info Chan 2
16 ASCII characters (2 per register) assigned to the unit identifier read as bytes.
Chan 1 ASCII Reading
Chan 2 ASCII Reading
6 ASCII characters (2 per register) reflecting the display readout.
VARIABLE
31007
BIT0
BIT1
BIT2
BIT4
BIT5
BIT6
BIT8
BIT9
BIT10
31008
BIT0
BIT1
BIT2
BIT3
BIT12
BIT13
BIT14
BIT15
31009
31010
33001
33002
40401-40408
40409-40416
40417-40419
40420-40422
ALIAS
READ FUNCTION CODE
OLCT 200 User Manual | 52
4
4
4
4
4
4
4
4
3
3
3
3
WRITE FUNCTION CODE
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA