Field Settings; Procedure; Detailed Description - Daikin EKCBX008BBV3 Installation Manual

Hide thumbs Also See for EKCBX008BBV3:
Table of Contents

Advertisement

12.9. Field settings

The unit shall be configured by the installer to match the installation
environment (outdoor climate, installed options, etc.) and user
demand. Thereto, a number of so called field settings are available.
These field settings are accessible and programmable through the
user interface on the indoor unit.
Each field setting is assigned a 3-digit number or code, for example
[1-03], which is indicated on the user interface display. The first digit
[1] indicates the 'first code' or field setting group. The second and
third digit [03] together indicate the 'second code'.
A list of all field settings and default values is given under
"12.10. Field settings table" on page
provided for 2 columns to register the date and value of altered field
settings at variance with the default value.
A detailed description of each field setting is given under
description" on page
24.

Procedure

To change one or more field settings, proceed as follows.
3
2
Press the z button for a minimum of 5 seconds to enter FIELD
1
SET MODE.
The $ icon (3) will be displayed. The current selected field
setting code is indicated ; (2), with the set value displayed to
the right - (1).
2
Press the bgi button to select the appropriate field
setting first code.
Press the bgj button to select the appropriate field
3
setting second code.
Press the pfi button and pfj button to change
4
the set value of the select field setting.
5
Save the new value by pressing the pr button.
6
Repeat step 2 through 4 to change other field settings as
required.
7
When finished, press the z button to exit FIELD SET MODE.
NOTICE
Changes made to a specific field setting are only stored
when the pr button is pressed. Navigating to a new field
setting code or pressing the z button will discard the
change made.
INFORMATION
Before shipping, the set values have been set as
shown under
"12.10. Field settings table" on page
When exiting FIELD SET MODE, "88" may be
displayed on the user interface LCD while the unit
initialises itself.
Installation manual
24
35. In this same list, we
"Detailed
1
35.

Detailed description

[0] User permission level
If required, certain user interface buttons can be made unavailable for
the user.
Three permission levels are defined (see the table below). Switching
between level 1 and level 2/3 is done by simultaneously pressing
buttons pfi and pfj immediately followed by
simultaneously pressing buttons s and ba, and keeping all 4
buttons pressed for at least 5 seconds (in normal mode). Note that no
indication on the user interface is given. When level 2/3 is selected,
the actual permission level – either level 2 or level 3 – is determined
by the field setting [0-00].
Button
Quiet mode button
s
Weather dependent
ba
set point button
Schedule timer
pr
enable/disable button
Programming button
<
pf
Time adjust buttons
i
pf
j
Inspection/test
z
operation button
[1] Weather dependent set point
The weather dependent set point field settings define the parameters
for the weather dependent operation of the unit. When weather
dependent operation is active the water temperature is determined
automatically depending on the outdoor temperature: low outdoor
temperatures will result in warmer water and vice versa. During
weather dependent operation, the user has the possibility to shift up
or down the target water temperature by a maximum of 5°C. See the
operation manual for more details on weather dependent operation.
Field settings for heating operation
■ [1-00] Low ambient temperature (Lo_A): low outdoor
temperature.
■ [1-01] High ambient temperature (Hi_A): high outdoor
temperature.
■ [1-02] Set point at low ambient temperature (Lo_Ti): the
target outgoing water temperature when the outdoor
temperature equals or drops below the low ambient
temperature (Lo_A).
Note that the Lo_Ti value should be higher than Hi_Ti, as for
low outdoor temperatures (i.e. Lo_A) warmer water is
required.
■ [1-03] Set point at high ambient temperature (Hi_Ti): the
target outgoing water temperature when the outdoor
temperature equals or rises above the high ambient
temperature (Hi_A).
Note that the Hi_Ti value should be lower than Lo_Ti, as for
warmer outdoor temperatures (i.e. Hi_A) less warm water
suffices.
Permission level
1
2
3
operable
operable
operable
operable
operable
operable
operable
EKCBX/H008BBV3
Unit for air to water heat pump system
4PW66983-1C – 08.2011