Figure 8.12 Site Wiring Diagram
1) SINGLE BOILER INSTALLATION, ON/OFF OR HIGH/LOW OPERATION VIA REMOTE TIME CLOCK CONTROL.
230V AC 50Hz
SUPPLY
N
FUSED ISOLATOR
N
L
2) MULTIPLE BOILER INSTALLATION, ON/OFF OR HIGH/LOW OPERATION VIA HAMWORTHY HEATING LIMITED MILTON BOILER SEQUENCE CONTROL.
NOTE: ROTARY SWITCH 'SW1' ON THE SEQUENCING INTERFACE MODULE - POSITIONS '1' TO '9' SETS THE BOILER FIRING ORDER.
BOILER NUMBER 1
SEQUENCING INTERFACE MODULE
SEQUENCING INTERFACE MODULE TERMINALS
BOILER PCB TO 'SIM'
INTERFACE TERMINALS
1
2
3
4
5
WIRING HARNESS
TO BOILER MAIN PCB
CONNECTOR 'C1-C8'
BOILER MAIN SITE
BOILER PCB PLUG/
WIRING TERMINALS
SOCKET TERMINALS
230V AC 50Hz
230V AC 50Hz
SUPPLY
N
L
G1
INTERLOCK
CONTROLS
N
L
NOTE: VOLT FREE CONTACT TERMINALS
NOT SHOWN FOR CLARITY.
3) MULTIPLE BOILER INSTALLATION, ON/OFF OR HIGH/LOW OPERATION VIA NON HAMWORTHY HEATING LIMITED BOILER SEQUENCE CONTROL.
BOILER NUMBER 1
BOILER SITE WIRING TERMINALS
BOILER MAIN SITE
BOILER PCB PLUG/
WIRING TERMINALS
SOCKET TERMINALS
230V AC 50Hz
230V AC 50Hz
SUPPLY
OUTPUT
N
L
G1
G2
SEQUENCER
BLR 1 ON/OFF
CONTACT
N
L
HAMWORTHY HEATING LTD
BOILER SITE WIRING TERMINALS
BOILER MAIN SITE WIRING TERMINALS - PLUG BRACKET
VOLT FREE SIGNAL OUTPUTS
RATED UP TO 250V AC 5A
L
15
16
17
18
19
20
LOW VOLTAGE
ROTARY SWITCH
INPUTS/OUTPUTS
SW1
8
6
7
8
9
10
NOT
UTILISED
OUTPUT
G2
G3
G4
SAFETY
BOILER MAIN SITE
WIRING TERMINALS
230V AC 50Hz
SUPPLY
G3
G4
N
SEQUENCER
BLR 1 HIGH/OW
CONTACT
SAFETY
INTERLOCK
CONTROLS
N
BOILER PCB PLUG/
SOCKET TERMINALS
230V AC 50Hz
OUTPUT
21
31
32
33
34
G1
G2
SAFETY INTERLOCK
SEQUENCING INTERFACE MODULE
SEQUENCING INTERFACE MODULE TERMINALS
BOILER PCB TO 'SIM'
INTERFACE TERMINALS
1
2
3
4
WIRING HARNESS
TO BOILER MAIN PCB
CONNECTOR 'C1-C8'
BOILER MAIN SITE
WIRING TERMINALS
230V AC 50Hz
SUPPLY
N
L
N
L
BOILER NUMBER 2
BOILER SITE WIRING TERMINALS
BOILER PCB PLUG/
SOCKET TERMINALS
230V AC 50Hz
OUTPUT
L
G1
G2
G3
G4
SEQUENCER
BLR 2 HIGH/OW
CONTACT
SEQUENCER
SAFETY
BLR 2 ON/OFF
INTERLOCK
CONTACT
CONTROLS
L
12
WESSEX 100 M
G3
G4
REMOTE CONTROL LOOPS.
NOTE: TERMINALS 'G1' AND 'G3' ARE
SUPPLIED WITH 230V AC.
MAINS VOLTAGE
MUST NOT
ONTO THESE TERMINALS!
REMOTE
CONTROLS
TIME CLOCK
BOILER NUMBER 2
LOW VOLTAGE
ROTARY SWITCH
INPUTS/OUTPUTS
5
6
7
8
9
10
NOT
UTILISED
BOILER PCB PLUG/
SOCKET TERMINALS
230V AC 50Hz
OUTPUT
CN16
G1
G2
G3
G4
SAFETY
INTERLOCK
CONTROLS
BOILER NUMBER 3
BOILER SITE WIRING TERMINALS
BOILER MAIN SITE
WIRING TERMINALS
SOCKET TERMINALS
230V AC 50Hz
SUPPLY
N
L
G1
N
L
BE FED
SW1
8
TO HAMWORTHY HEATING LIMITED
MILTON BOILER SEQUENCE CONTROL
(REFER TO MILTON INSTALLATION
MANUAL FOR FURTHER DETAILS)
BOILER PCB PLUG/
230V AC 50Hz
OUTPUT
G2
G3
G4
SEQUENCER
BLR 3 HIGH/OW
CONTACT
SEQUENCER
SAFETY
BLR 3 ON/OFF
INTERLOCK
CONTACT
CONTROLS
500001080/F