10.2.4.
required
To retain fan coil values through a power out set SW2-4 and SW2-5 both OFF.
To re-load fan coil values from the IO_Interface inputs after a power out set SW2-4 ON and SW2-5 ON.
This option is not available (or needed) when using Energy Save Deaband Mode.
10.2.5.
SW2-6 OFF: The heating / cooling output relay and the LED5 will energise when the unit is in cooling mode or in auto
cooling mode.
SW2-6 ON: The heating / cooling output relay and the LED5 will energise when the unit is in heating mode or in auto
heating mode.
10.3.

Revision History:

Ver 1.00
Ver 1.01
SW2-4 and SW2-5 Reset settings when energy save deadband mode is not

SW2-6 Heating / Cooling Output

th
28
May 2010
th
14
September 2010
Final version
Added 10.2.4 (SW2-4 and SW2-5 reset settings)
Page 23 of 24