Toshiba MCY-MAP0401TP Series Installation Manual page 7

Multi type outdoor units
Table of Contents

Advertisement

2FAN_IM_DB04905901-00.book Page 6 Friday, October 24, 2014 3:19 PM
 Necessary space for installation
(Unit: mm)
Obstacle at rear side
Upper side is free
1. Single unit installation
2. Obstacles on both right and left sides
The height of the
obstacle should be
lower than the height
of the outdoor unit.
150 or more
300 or more
3. Serial installation of two or more units
The height of the obstacle should be lower than the
height of the outdoor unit.
300 or
300 or
300 or
150 or
more
more
more
more
Obstacle also above unit
150 or
more
EN-11
Obstacle in front
Above unit is free
1. Single unit installation
2. Serial installation of two or more units
Obstacle also above unit
1,000 or more
Obstacles in both front and rear of unit
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the
unit, should be lower than the height of the outdoor unit.
Standard installation
1. Single unit installation
2. Serial installation of two or more units
300 or
300 or more
more
 Installation of outdoor unit
• Before installation, check the strength and horizontalness of the base so that abnormal sounds do not
emanate.
• According to the following base diagram, fix the base firmly with the anchor bolts.
(Anchor bolt, nut: M10 x 4 pairs)
150
– 6 –
Installation Manual
Serial installation in front and rear
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the
unit should be lower than the height of the outdoor unit.
Standard installation
1,000 or
300 or
1,500 or
2,000 or
more
more
more
more
Back side
600
150
525
Drain hole
45
Kno ckout hole
200 or
more
EN-12

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mcy-map0501tp seriesMcy-map0601tp series

Table of Contents