2FAN_IM_DB04905901-00.book Page 10 Friday, October 24, 2014 3:19 PM
Connecting pipe size of indoor unit
Capacity rank
Branching section
Indoor unit
007 to 012 type
(3)
connecting
Indoor unit
pipe
014 to 018 type
020 to 056 type
Selection of branching section (Y-shaped branching joint)
Y-shaped
(4)
Branching section
branching
joint
Y-shape branch joint
Selection of branching section (Branching header)
Branching
(5)
Branching section
header
Branching header
(*1)For each line after branch header, total indoor capacity code
must be 6.0 or less
 Selection of refrigerant piping for quiet place (with PMV Kit)
Outdoor unit
Main
Branching
Branching
pipe
pipe
(2)
header
(1)
1st branching
section
(4)
(3)
Branching pipe
(2)
Y-shaped
branching joint
EN-19
Gas pipe
Liquid pipe
9.52
6.35
12.70
6.35
15.88
9.52
Model name
RBM-BY55E
Model name
For 4 branches
RBM-HY1043E
For 8 branches(*1)
RBM-HY1083E
(4)
PMV Kit
(3)
(3)
(3)
Indoor unit
(3)
(3)
(4)
No.
Piping parts
Name
Size of main pipe
Outdoor unit
Outdoor unit capacity type
(1)
Main pipe
1st branching
section
Pipe size between branching sections
Total capacity codes of
indoor units at down stream
Branching section
Branching
(2)
pipe
Equivalent to
Branching section
Below 2.4
2.4 or more
Below 6.4
Connecting pipe size of indoor unit
Branching section
Indoor unit
(3)
connecting
Indoor unit
pipe
Selection of branching section (Y-shaped branching joint)
Y-shaped
(4)
Branching section
branching
joint
Selection of branching section (Branching header)
Branching
(5)
Branching section
header
Branching header
(*1)For each line after branch header, total indoor capacity code
must be 6.0 or less
Selection of PMV Kit
(6)
PMV Kit
PMV Kit
* PMV kit can be connected less than 056 type FCU.
– 10 –
Installation Manual
Selection of pipe size
Same as connecting
Gas pipe
Liquid pipe
pipe size of the outdoor
0401 type
15.88
9.52
unit.
0501 type
15.88
9.52
0601 type
19.05
9.52
Pipe size differs based
on the total capacity
code value of indoor
units at the downstream
side
Gas pipe
Liquid pipe
side. If the total value
Equivalent to
exceeds the capacity
HP
capacity
code of the outdoor unit,
apply the capacity code
Below 6.4
12.70
9.52
of the outdoor unit. (See
Below 6.4
15.88
9.52
Table 1 and 2.)
6.4 or more
19.05
9.52
Capacity rank
Gas pipe
Liquid pipe
007 to 012 type
9.52
6.35
014 to 018 type
12.70
6.35
020 to 056 type
15.88
9.52
Model name
Y-shape branch joint
RBM-BY55E
Model name
For 4 branches
RBM-HY1043E
For 8 branches(*1)
RBM-HY1083E
Capacity rank
Model name
007 to 014 type
RBM-PMV0362E
015 to 056 type
RBM-PMV0902E
Remarks
EN-20