Switch setting (setting example when controlling 2 or more refrigerant lines centrally)
Outdoor units (setting manually)
Outdoor unit's
Outdoor unit
interface P.C. board
SW13, 14
1
(Line (system) address)
Dip switch 2 of SW30
(Terminator of indoor /
outdoor communication
ON
line and central control
line)
Connect after setting
Connect after setting
Relay connector
addresses.
Outdoor unit
Outdoor unit
[U1, U2] and
[U1, U2] and
[U3, U4] connected
[U3, U4] connected
U3
U4
CN10
CN02
U1
U2
U1
U
1
U
2
U
1
U
2
U
1
A
B
A
B
Remote
Remote
Remote
controller
controller
controller
Individual
Indoor units
(automatic setting)
Line (system) address
1
Indoor unit address
1
Group address
0
CAUTION
Relay connector connection
Never connect relay connectors between the [U1, U2] and [U3, U4] terminals before completing address setting of all
the refrigerant lines. Otherwise, the addresses cannot be set correctly.
EN-43
*The items in bold font must be set manually.
Outdoor unit
Outdoor unit
Factory default
2
3
1
Set to OFF
Set to OFF after
after setting
ON
setting addresses.
addresses.
Connect after setting
Open
addresses.
addresses.
Central
controller
Outdoor unit
[U1, U2] and
[U3, U4] connected
U3
U4
U3
U4
CN10
CN10
CN02
CN02
U2
U1
U2
U
2
U
1
U
2
U
1
U
2
A
B
A
B
A
B
Remote
controller
Group
1
2
2
3
2
1
2
1
0
1
2
0
 Manual address setting with the remote controller
Procedure when setting indoor units' addresses first under the condition that indoor wiring has been completed and
outdoor wiring has not been started (manual setting using the remote controller)
Wiring example of 2 refrigerant lines
Refrigerant line 1
Outdoor
unit
Indoor unit 1
Remote
controller
Line (system) address
1
Indoor unit address
1
1
Group address
Header unit
In the example above, disconnect the remote controller connections between the indoor units and connect a
wired remote controller to the target unit directly before address setting.
2, 5, 8
SET DATA
4, 7, 10
11
Pair the indoor unit to set and the remote controller one-to-one.
Turn on the power.
1
Push and hold the
,
, and
buttons at the same time for more than 4 seconds.
LCD starts flashing.
– 22 –
Installation Manual
Refrigerant line 2
Outdoor
unit
Indoor unit 2
Indoor unit 3
Indoor unit 1
Indoor unit 2
1
1
2
2
2
3
1
2
2
2
2
2
Follower unit
Follower unit
Follower unit
Follower unit
CODE No.
SET
DATA
SETTING
UNIT No.
R.C.
No.
CODE No.
TEMP.
ON / OFF
3, 6, 9
TIMER SET
TIME
FILTER
RESET TEST
SET CL
1
EN-44