Protection Mm; Protection Against Instantaneous Short-Circuit "Iinst; Summary Table Of Protection Functions For Pr332 And Pr333/P - ABB Tmax T7 Operating Instructions Manual

T7-t8-x1 low voltage air circuit breakers protection releases
Hide thumbs Also See for Tmax T7:
Table of Contents

Advertisement

WARNING: For three-pole circuit-breakers without external neutral, the Neutral protection setting must be OFF,
otherwise the sensor presence error will be signalled (Error CS).
In these cases, short-circuit T5-T6 on the sliding contacts, as shown in the wiring diagrams.
WARNING: Failure to comply with the setting limits of "I1" and "InN" may result in damage to the circuit-break-
er and consequent risks even for the operator.
WARNING: the protection setting is automatically 100% when the current value exceeds 15.5xIn on the neutral.

3.6.21. Protection MM

The protection, available with PR332/P MM releases, protects against short-circuit.
In order to function, it must be enabled via the display menu and activated by means of a signal supplied to inputs K14/K15:
- Signal High: protection activated;
- Signal Low: protection deactivated.
The release handles output contacts 95S/98s as feedback of the protection state, so as to communicate whether it is activated
(contacts closed) or deactivated (contacts open).
The state of the input contacts is available in the Test-MM Test-Input menu.
Further details about the electrical characteristics of the inputs and outputs are available in chapter 3.8.4.

3.6.22. Protection against instantaneous short-circuit "Iinst"

The purpose of this protection is to maintain the integrity of the circuit-breaker and installation in the case of particularly high
current values requiring shorter reaction times than those provided by the instantaneous short-circuit-protection.
The protection cannot be disabled. It has a single fixed time protection curve and the threshold level is exclusively at the charge
of ABB personnel.

3.6.23. Summary table of protection functions for PR332 and PR333/P

Current
protections
L
all curves:
      
t=k/I2 and
IEC 60255-3
S
      
(t=k)
S
      
(t=k/I
)
2
S2
      
(t=k)
D
      
(t=k)
I
      
(t=k)
MCR
      
(t=k)
G
(4) (6)
      
(t=k)
B0431
Mod.
Trip Threshold
0,4xIn ≤ I
≤ 1xIn
1
step 0,01xIn
0,6xIn ≤ I
≤10xIn
2
step 0,1xIn
0,6xIn ≤ I
2 start-up
≤10xIn
step 0,1xIn
0,6xIn ≤ I
≤10xIn
2
step 0,1xIn
0,6xIn ≤ I
≤10xIn
2
step 0,1xIn
0,6xIn ≤ I
≤10xIn
7
step 0,1xIn
1,5xIn ≤ I
≤15xIn
3
step 0,1xIn
1,5xIn ≤ I
3 Start-Up
15x In
6,0xIn ≤ I
≤15xIn
5
step 0,1xIn
0,1xIn ≤ I
≤1xIn
4
step 0,02xIn
B1751
Trip time
3s ≤ t
≤ 144s
, step 3s
(1)
1
@I
=3I
f
1
I
>I2
f
0,05s ≤ t
≤ 0,8s, step 0,01s
2
0,10s ≤ t
≤ 30s, step
2 start-up
0,01s
0,04s ≤ t
≤ 0,2s, step 0,01s
2 sel
0,05s ≤ t
≤ 0,8s,
2
step 0,01 s @I
=10In
f
@I
>I
f
2
0,05s ≤ t
≤ 0,8s, step 0,01s
2
0,10s ≤ t
≤ 30s, step
2 start-up
0,01s
0,04s ≤ t
≤ 0,4s, step 0,05s
2 sel
@I
>I
f
7
0,20s ≤ t
≤ 0,8s, step 0,01s
7
0,10s ≤ t
≤ 30s, step
7 start-up
0,01s
0,13s ≤ t
≤ 0,5s, step 0,01s
7 sel
≤ 30 ms
0,1s ≤ t
≤ 30s, step
3 start-up
0,01s
@ I
>I
f
3
@I
>I
f
5
≤ 30ms
(3)
0,1s ≤ t
≤-1s, step 0,05 s
4
0,1s ≤-t
≤ 1s, step 0,02s
4 start-up
0,04s ≤ t
≤ 0,2s, step 0,01s
4 sel
@ I
>I
f
4
Apparatus
Emax X1-Tmax T7-Tmax T8
1SDH000587R0002
Doc N°
Trip
Trip time
threshold
tolerance
tolerance
(2)
Releasebe-
≤ 6In
±10%, I
tween 1,05
f
-> 6In
±20%, I
and 1,2 xI1
f
The best of the
≤ 6In
±7%, I
f
two data±10%
±10%, I
> 6In
f
or 40ms
≤ 6In
≤ 6In
±7%, I
±15%, I
f
f
±10%, I
> 6In
±20%, I
-> 6In
f
f
The best of the two
≤ 6In
±7%, I
data
f
±10% or
±10%, I
> 6In
f
40ms
The best of the
±10%
two data±10%
or 40ms
±10%
±10%
The best of the
±7%
two data±10%
or 40ms