Operating Icons - ABB Tmax T7 Operating Instructions Manual

T7-t8-x1 low voltage air circuit breakers protection releases
Hide thumbs Also See for Tmax T7:
Table of Contents

Advertisement

The following table describes all the messages that could appear on the display in a pop-up window after an unallowed attempt
to configure parameters or settings.
Alarm message
Password error
Session impossible
Value off range
Failed 1001/2001
Failed 1002/2002
Failed 1006/2006
Failed 1005/2005
Failed 1009/2009
Failed 1003/2003
Failed 1004/2004
Failed 3001
Failed 3002
Failed 3003
Exception 6
Unavailable
Invalid date
Parameters revised
Cancelled
Failed
3.4.3.3.

Operating icons

An area with icons showing the operating conditions of the protection release is available on the display.
The area is at the bottom right of the display (See par. 1.4.3 Display Ref.5) and includes 4 positions in which the icons can be shown.
Starting from the position on the far right, a description of the available icons is given below:
Position
Icon
Condition
OFF
1
ON (Fixed)
(right)
ON
(Flashing @1Hz)
OFF
2
ON
OFF
3
ON
OFF
ON
4
(left)
OFF
ON
B0431
Mod.
Description
A programming session cannot be started due to a contingency (e.g. a timer-controlled delay
still elapsing)
Value beyond the established limits
Inconsistency between thresholds of protections L and S (SETA/SETB)
Inconsistency between thresholds of protections I and S (SETA/SETB)
Inconsistency between thresholds of protections I and D (SETA/SETB)
Inconsistency between thresholds of protections L and D (SETA/SETB)
SdZ incompatible SdZ directional
Inconsistency between thresholds of protections L and S2 (SETA/SETB)
Inconsistency between thresholds of protections I and S2 (SETA/SETB)
Problems with language change
Problems with toroid RC setting
Problems with neutral setting
Control momentarily unavailable
Function temporarily unavailable
Date and time not updated. Set them.
Programming session concluded correctly
Programming session cancelled
Programming session rejected
Description
Datalogger function deactivated
Datalogger function activated, awaiting an event to record
Datalogger function activated with recording completed and waiting to save data
or restart
Dual set deactivated. One single configuration set is available for adjusting the
protections
Dual set activated. Two configuration sets are available for adjusting the protec-
tions
The icon depicting the operative configuration set ([A] or [B]) is displayed
External Vaux power source absent
External Vaux power source present
Editing of parameters and settings via the local mode. No update in progress
Editing of parameters and settings via the local mode. Update in progress: the
icon appears if the users has changed some of the parameters but has not yet
completed the operation by selecting CONFIRM. The icon only disappears after
the changes ave been confirmed or annulled
Editing of parameters and settings via the local mode. No update in progress
Editing of parameters and settings via the remote mode (only activated if the
PR330/D-M module is installed)
B1751
Apparatus
Emax X1-Tmax T7-Tmax T8
1SDH000587R0002
Doc N°
Scale
Page No
26/66