6 SEQUENTIAL TESTING
Using Testire to carry out a Sequential Test means that a number of operations (Smoke, Heat
and Clearing) can be pre-programmed into the unit before it is raised up to the detector. This
saves time, reduces handling and enables the testing of certain multi-sensor detectors.
6.1 SMOKE TEST + CLEARING
1
Select smoke test from the main menu
by moving the cursor to smoke. Press the
enter key to select smoke.
Smoke 1
Heat
Clear
Menu
NOTE
To delete a test sequence, simply press
the escape key to cancel your selection.
www.detectortesters.com/testifire
16
2
Move the cursor down to clear and
press the enter key to select clear.
Status
NOTE
The rst stimulus selected will be indicated
by the number 1 beside it. The next
stimulus in the sequential test will be
indicated by the number 2 beside it.
Smoke 1
Heat
Clear 2
Menu
Status
3
The initial smoke test will begin automatically
when the head unit is placed over the
detector, breaking the infrared beam.