Technical specifications
Article number
–
Number of connectable IO Devices,
max.
–
Of which IO devices with IRT, max.
–
Number of connectable IO Devices for
RT, max.
–
of which in line, max.
–
Number of IO Devices that can be sim-
ultaneously activated/deactivated, max.
–
Number of IO Devices per tool, max.
–
Updating times
Update time for IRT
–
for send cycle of 250 µs
–
for send cycle of 500 µs
–
for send cycle of 1 ms
–
for send cycle of 2 ms
–
for send cycle of 4 ms
–
With IRT and parameterization of "odd"
send cycles
Update time for RT
–
for send cycle of 250 µs
–
for send cycle of 500 µs
–
for send cycle of 1 ms
–
for send cycle of 2 ms
–
for send cycle of 4 ms
PROFINET IO Device
Services
–
PG/OP communication
–
S7 routing
–
Isochronous mode
–
Open IE communication
–
IRT
–
MRP
–
MRPD
–
PROFIenergy
–
Shared device
42
6ES7517-3TP00-0AB0
512; In total, up to 1 000 distributed I/O devices
can be connected via AS-i, PROFIBUS or
PROFINET
64
512
512
8; in total across all interfaces
8
The minimum value of the update time also
depends on communication share set for
PROFINET IO, on the number of IO devices, and
on the quantity of configured user data
250 µs to 4 ms
500 µs to 8 ms
1 ms to 16 ms
2 ms to 32 ms
4 ms to 64 ms
Update time = set "odd" send clock (any multiple
of 125 µs: 375 µs, 625 µs ... 3 875 µs)
250 µs to 128 ms
500 µs to 256 ms
1 ms to 512 ms
2 ms to 512 ms
4 ms to 512 ms
Yes
Yes
No
Yes
Yes
Yes
Yes; Requirement: IRT
Yes
Yes
CPU 1517T-3 PN/DP (6ES7517-3TP00-0AB0)
Manual, 12/2017, A5E36285525-AB