Technical specifications
Article number
I/O address area
Inputs
•
Outputs
•
per integrated IO subsystem
–
Inputs (volume)
–
Outputs (volume)
per CM/CP
–
Inputs (volume)
–
Outputs (volume)
Subprocess images
Number of subprocess images, max.
•
Hardware configuration
Number of distributed IO systems
Number of DP masters
integrated
•
Via CM
•
Number of IO Controllers
integrated
•
Via CM
•
Rack
Modules per rack, max.
•
Number of lines, max.
•
PtP CM
Number of PtP CMs
•
Time of day
Clock
Type
•
Backup time
•
Deviation per day, max.
•
40
6ES7517-3TP00-0AB0
32 kbyte; All inputs are in the process image
32 kbyte; All outputs are in the process image
16 kbyte; 16 KB via the integrated PROFINET IO
interface X1, 8 KB via the integrated
PROFINET IO interface X2 and via the integrated
PROFIBUS DP interface
16 kbyte; 16 KB via the integrated PROFINET IO
interface X1, 8 KB via the integrated
PROFINET IO interface X2 and via the integrated
PROFIBUS DP interface
8 kbyte
8 kbyte
32
64; A distributed I/O system is characterized not
only by the integration of distributed I/O via
PROFINET or PROFIBUS communication
modules, but also by the connection of I/O via
AS-i master modules or links (e.g. IE/PB-Link)
1
8; A maximum of 8 CMs/CPs (PROFIBUS,
PROFINET, Ethernet) can be inserted in total
2
8; A maximum of 8 CMs/CPs (PROFIBUS,
PROFINET, Ethernet) can be inserted in total
32; CPU + 31 modules
1
the number of connectable PtP CMs is only
limited by the number of available slots
Hardware clock
6 wk; At 40 °C ambient temperature, typically
10 s; Typ.: 2 s
CPU 1517T-3 PN/DP (6ES7517-3TP00-0AB0)
Manual, 12/2017, A5E36285525-AB