Bending Conduit - Greenlee 1800 Mechanical Bender Instruction Manual

1/2" through 1" rigid and imc conduit
Table of Contents

Advertisement

Bending Conduit

STUB TO
BOTTOM
OF CONDUIT
STUB LENGTH
MARK
DEDUCT
NO. 2
To Locate Bending Marks for Stubs
1. See the Stub Dimensions Table for the minimum stub length. The desired stub must be equal to or greater
than the minimum stub length.
2. See the Stub Illustrations. Measure and mark the stub length on the conduit. This is mark 1. Subtract the
deduct from the stub length and make mark 2. Mark 2 is the bending mark — locate this mark at the front
edge of the hook.
Stub Dimensions Table
Conduit Size
Shoe Radius
1/2"
2-5/8"*
3/4"
4-5/8"
1"
5-7/8"
Figures are approximate
* To meet electrical code, bend 1/2" diameter conduit in the 3/4" position to produce a bend with a radius greater than 4".
Greenlee / A Textron Company
ALIGN BENDING
MARK WITH
FRONT EDGE
OF HOOK
MARK
NO. 1
Minimum
Deduct
Stub Length
6-1/2"
5-1/2"
9-1/2"
8-1/2"
12"
1800 Mechanical Bender
Minimum Distance
from End of Conduit
1"
11"
6
4455 Boeing Dr. • Rockford, IL 61109-2988 USA • 815-397-7070