7
Sensing Labs SenlabA 4MA-LAB-xxNS – User guide – Version 2 – REV D
Battery replacement (Indoor version only)
Replacement battery must by a Lithium 3,6V AA type with 50mA min of supported
continuous current  Contact your distributor to get original battery reference.
Indoor V2 have the capability to keep activation status during a few minutes, so the
process is:
1. Open the casing
2. Remove the old battery and, during the same minute, put the new battery
3. Check if the device activation is still OK (see "Activation of the device" chapter)
4. In case activation lost, you need to activate the device again
5. Close the casing
1. Send the configuration request "request_reset_battery_level" to the device, using
your application
ATTENTION:
EN: There is a risk of explosion if the battery is replaced by an incorrect type. Dispose of
used batteries according to instructions.
FR: Il y a risque d'explosion si la batterie est remplacée par une batterie de type incorrect.
Mettre au rebut les batteries usagées conformément aux instructions.
Security

Electrical safety

All circuits are SELV (Safety extra low voltage), including interface circuits which are only
used for measurement (signals without power, these circuits are considered LPS).
Ambient temperature of use
The ambient temperature of use is comprised between 0°C and +55°C.