PGN 65010 – Utility Phase B AC Power
The ACM100 uses this PGN to transmit the real power and apparent power (the vector sum of
real power and reactive power) for phase B when the ACM100's AC Device Type is configured
to "Utility".
Field 1: Real Power – This field indicates the real power delivered by the AC power source in
units of 1W.
2: Apparent Power – This field indicates the apparent power delivered by the AC power
source in units of 1 VA.
PGN 65013 – Utility Phase A AC Power
The ACM100 uses this PGN to transmit the real power and apparent power (the vector sum of
real power and reactive power) for phase A when the ACM100's AC Device Type is configured
to "Utility".
Field 1: Real Power – This field indicates the real power delivered by the AC power source in
units of 1W.
2: Apparent Power – This field indicates the apparent power delivered by the AC power
source in units of 1 VA.
PGN 65016 – Utility Total AC Power
The ACM100 uses this PGN to transmit the total real power and apparent power (the vector sum
of real power and reactive power) when the ACM100's AC Device Type is configured to "Utility".
Field 1: Real Power – This field indicates the real power delivered by the AC power source in
units of 1W.
2: Apparent Power – This field indicates the apparent power delivered by the AC power
source in units of 1 VA.
PGN 65020 – Generator Phase C AC Power
The ACM100 uses this PGN to transmit the real power and apparent power (the vector sum of
real power and reactive power) for phase C when the ACM100's AC Device Type is configured
to "Generator".
Field 1: Real Power – This field indicates the real power delivered by the AC power source in
units of 1W.
2: Apparent Power – This field indicates the apparent power delivered by the AC power
source in units of 1 VA.
PGN 65023 – Generator Phase B AC Power
The ACM100 uses this PGN to transmit the real power and apparent power (the vector sum of
real power and reactive power) for phase B when the ACM100's AC Device Type is configured
to "Generator".
Field 1: Real Power – This field indicates the real power delivered by the AC power source in
units of 1W.