2: Power Factor – This field indicates the magnitude of the power factor supplied by the
source in units of 1/16384 (dimensionless).
3: Power Factor Lagging – This field indicates whether the specified power factor is
lagging or leading.
PGN 65028 – Generator Total AC Reactive Power
The ACM100 uses this PGN to transmit total reactive power and power factor information when
the ACM100's AC Device Type is configured to "Generator".
Field 1: Reactive Power – This field indicates the reactive power delivered by the source in
units of 1 VAr.
2: Power Factor – This field indicates the magnitude of the power factor supplied by the
source in units of 1/16384 (dimensionless).
3: Power Factor Lagging – This field indicates whether the specified power factor is
lagging or leading.
PGN 65005 – Utility Total AC Energy
The ACM100 uses this PGN to transmit the total energy delivered by the power source when
the ACM100's AC Device Type is configured to "Generator".
Field 1: Total kWh Hours Export – This field indicates the total energy delivered by the AC
power source in units of 1 kWh.
2: Total kWh Hours Import – This field indicates the total energy delivered to the AC
power source in units of 1 kWh.
PGN 65018 – Generator Total AC Energy
The ACM100 uses this PGN to transmit the total energy delivered by the power source when
the ACM100's AC Device Type is configured to "Generator".
Field 1: Total kWh Hours Export – This field indicates the total energy delivered by the AC
power source in units of 1 kWh.
2: Total kWh Hours Import – This field indicates the total energy delivered to the AC
power source in units of 1 kWh.
PGN 65007 – Utility Phase C AC Power
The ACM100 uses this PGN to transmit the real power and apparent power (the vector sum of
real power and reactive power) for phase C when the ACM100's AC Device Type is configured
to "Utility".
Field 1: Real Power – This field indicates the real power delivered by the AC power source in
units of 1W.
2: Apparent Power – This field indicates the apparent power delivered by the AC power
source in units of 1 VA.
Page A6
Appendix A – NMEA 2000 Interfacing