Initialization screen

After the first power-on you have to
choose the mode of DALI Touch ME7
panel. You can choose either Tunable
White mode (TW mode) or RGB mode.
Furthermore you can choose whether
you would like to use the ambient light
sensor (closed loop) or not (open loop).
Select the DALI line you would like to
use. Multiple DALI lines can be selected.
Only DALI line 1 is internally biased. DALI
lines 2 and 3 needs external DALI power
supply.
Screen for addressing the ballast
depends on the mode selection – TW
or RGB. Press SCAN to start searching
process. All DALI devices present on
the DALI bus will appear the column on
the left with their corresponding DALI
addresses. Press the address to select
TW mode
preussen automation GmbH © 2016 | Flurweg 11 | 82402 Seeshaupt | Germany
6
TW control without sensor
TW control with sensor
RGB control
the DALI device. To identify DALI device
you use button IDENTIFY – DALI device
starts to periodically turn the light
on and off. Identification is aborted
by repeated press of the button. To
move DALI device into the groups for
TW or RGB control use corresponding
buttons: "warm / cold" for TW mode or
"red / green / blue" for RGB mode. The
selected DALI device then appears in the
corresponding column. Use arrows up
and down to scroll the columns. Whole
group of devices can be identified using
corresponding TEST button. To remove
DALI device from a group use trash
button. The deleted device will appear
back in the left column. After finishing
the selection of DALI devices into the
groups press OK.
Use trash button to remove
the device from group.
Use OK button to finish and
save the settings.