preussen automation DALI Touch ME7 User Manual page 14

Advertisement

DALI Touch ME7
When touch the arrows in the right part
of the screen you can scroll to the last
two buttons that deals with the timing
configuration of movement sensor and
the calibration of light sensor. These
settigns are valid only for closed loop
TW mode with correctly connected light
and movement sensor "MSensor2" by
Tridonic. Calibration and settings of the
sensor will be further described in final
user guide.
The calibration of ambient sensor
In the sensor calibration screen you will
see one row for each sensor that was
found on the DALI bus. The first number
is the address of the sensor. When
user presses the first input textbox
the brightness level will be set to 33 %
by broadcast. Now the user should
measure illuminance using the luxmeter
and type the illuminance value in lx into
the textbox. The situation repeats for
the next two textboxes with 66 % and
100 % brightness levels. After entering
the reference illuminance levels the
calibration is confirmed by pressing OK
button.