ABB REJ603 Product Manual page 9

Self-powered feeder protection, relion 605 series
Table of Contents

Advertisement

Self-powered feeder protection
REJ603
Product version: 3.0
Table 12.
Environmental conditions
Description
Operating temperature range
Short-time service temperature range
Relative humidity
Atmospheric pressure
Altitude
Transport and storage temperature range
Table 13.
Environmental tests
Description
Dry heat test (humidity < 50% )
Working
Storing
Dry cold test
Working
Storing
Damp heat test, cyclic
Change of temperature test
Table 14.
Electromagnetic compatibility tests
Description
1 MHz/100 kHz burst disturbance test:
Common mode
mode
Differential
Electrostatic discharge test:
Contact discharge
Air discharge
Conducted radio frequency interference
tests:
9
Value
-25...+55ºC
-40...+85ºC (<16 h)
Display viewable range : above -20 ºC up to
+70 ºC
< 93%, non-condensing
86...106 kPa
up to 2000 m
-40...+85ºC
Type test value
96 h at +70°C
96 h at +85°C
96 h at -25°C
96 h at -40°C
2 cycles (12 h + 12 h) at
+25°C...+55°C,
Rh > 93%
Cyclic : 3 hours at -25°C + 3
hours at +55°C ,
Number of cycles : 5
Type test value
2.5 kV, 400/40 pulses/s
1.0 kV, 400/40 pulses/s
4 kV, 150 pF/330 Ω
6 kV, 150 pF/330 Ω
10 V
f=150 KHz...80 Mhz
10 V
f=27, 68 MHz
Not applicable for low energy trip
output
1MDB07217-YN
Issued: 2017-11-21
Revision: E
Reference
IEC 60068-2-2
IEC 60068-2-1
IEC 60068-2-30
IEC 60068-2-14
Reference
IEC 61000-4-18, class III
IEC 60255-26
IEC 61000-4-2
IEC 60255-26
IEC 61000-4-6
ABB