Table 16.
Insulation tests
Description
Dielectric test
Test voltage
Test voltage for bi-stable
contact
Impulse voltage test
Test voltage
Test voltage for binary input
and bi-stable contact
Insulation resistance test
Isolation resistance
Protective bonding test
Resistance
Table 17.
Mechanical tests
Description
Vibration tests
Response
Endurance / Withstand
Shock tests
Response
Endurance / Withstand
Bump tests
Seismic test
Table 18.
Power supply module test
Description
Gradual shutdown and start up
11
Type test value
2 kV, 50 Hz, 1 min
0.5 kV, 50 Hz, 1 min
Not applicable for low energy trip
output
5 kV, 1.2/50 μs, 0.5 J
1 kV, 1.2/50 μs, 0.5 J
Not applicable for low energy trip
output
> 100 M Ω at 500 V DC
<0.1 Ώ, 20 A, 60 s
Type test value
10...150 Hz, 0.075 mm / 1.0g,
1 sweep / axis
10...150 Hz, 2.0 g,
20 sweeps / axis
5 g, 3 pulses in each direction
15 g, 3 pulses in each direction
10 g, 1000 bumps in each
direction
Type test value
Shut-down ramp: 60 s
Power off period: 300 s
Start-up ramp: 60 s
1MDB07217-YN
Issued: 2017-11-21
Revision: E
Reference
IEC 60255-27
IEC 60255-27
IEC 60255-27
IEC 60255-27
Reference
IEC 60255-21-1, class I
IEC 60255-21-2, class I
IEC 60255-21-2, class I
IEC 60255-21-3, class I
Reference
IEC 60255-26