ABB REJ603 Product Manual page 14

Self-powered feeder protection, relion 605 series
Table of Contents

Advertisement

Self-powered feeder protection
REJ603
Product version: 3.0
Table 24.
Very high-set phase overcurrent protection, stage I>>> / 50-2
Parameter
Setting range of pick-up current 'I >>>'
Operation accuracy
1)
Operation mode
Operate time delay (DMT) 't >>>'
Operation time accuracy
1)
Reset ratio
1)
Operation time accuracy for protection functions when relay is in energised condition.
Table 25.
Low-set earth-fault protection, stage I0> / 51N
Parameter
Setting range of pick-up current 'I0 >'
Operation accuracy
1)
Operate time delay (DMT) 't0 >'
Operation time accuracy
1)
Operating curve type
Time multiplier setting 'k0'
Operation time accuracy
1)
IEC, ANSI, HR, FR characteristics
RI characteristics
IEC, ANSI, HR, FR characteristics
RI characteristics
Reset ratio
1)
Operation time accuracy for protection functions when relay is in energised condition.
14
Value (Range)
0.2...32.0 x In in steps 0.001, infinite for CT variant
± 3.0% x In for value < 1.2 In , ± 3.0% x I for value ≥ 1.2 In
Definite time, Instantaneous
0.04...64 s in steps of 0.01
± 2.0% of set value or ± 30 ms
0.98
Value (Range)
External earth measurement (through CBCT or residual connection) :
0.01...2.0 x In in steps 0.01, infinite
Internal earth measurement : 0.1...2.0 x In in steps 0.01, infinite
External earth measurement : ± 3.0% x In for value < 1.2 In ,
± 3.0% x I for value ≥ 1.2 In
Internal earth measurement : ± 9.0% x In for value < 1.2 In ,
± 9.0% x I for value ≥ 1.2 In
0.04...64 s in steps of 0.01
External earth measurement : ± 2.0% of set value or ± 30 ms
Internal earth measurement : ± 10.0% of set value or ± 30 ms
IEC 60255-151:
Normal inverse, Very inverse, Extremely inverse, Long-time inverse
ANSI C37.112:
Moderate inverse, Normal Inverse, Very inverse, Extremely inverse
Special curves:
RI inverse, HR fuse, FR fuse
0.02...1.6, in steps of 0.01
External earth measurement : class E(5) or ± 30 ms
External earth measurement : class E(7.5) or ± 30 ms
Internal earth measurement : ± 5.0% of set value or ± 30 ms
Internal earth measurement : ± 10.0% of set value or ± 30 ms
IDMT : 0.96 and DT : 0.98
1MDB07217-YN
Issued: 2017-011-21
Revision: E
ABB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents