Self-powered feeder protection
REJ603
Product version: 3.0
13. Technical data
Table 5.
Dimensions
Relay type Description
Width
Height
Depth
Weight
Table 6.
Power supply for remote trip function (optional functionality with external power supply)
Description
Uaux nominal
Uaux variation
Burden of auxiliary voltage supply under
quiescent (Pq)/operating condition
Ripple in the DC auxiliary voltage
Table 7.
Energizing inputs
Description
Rated frequency
Current inputs
Rated current,
Thermal withstand capability:
Input burden in CT powered circuit
Input impedance for measuring input
7
Value
frame
case
frame
case
case
relay
Value
24...240 V AC, 50 and 60 Hz
24...240 V DC
85...110% of Uaux (20.4...264 V AC)
80...120% of Uaux (19.2...288 V DC)
< 2.0 W / < 4.5 W
Max 15% of the DC value (at frequency of 100 Hz)
In
Continuous
For 1 s
For 10 s
1MDB07217-YN
Issued: 2017-11-21
132.5 mm
121.5 mm
167.0 mm
137.0 mm
182.5 mm
2.96 kg
Value
50/60 Hz
1 A
5A
2.5 A
12.5 A
100 A
500 A
20 A
100 A
2.5 VA
2.5 VA
< 100 m Ω
< 20 m Ω
Revision: E
ABB