Carrier 40MPHA Service Manual page 19

High wall ductless system sizes 09 to 12
Hide thumbs Also See for 40MPHA:
Table of Contents

Advertisement

ERROR DIAGNOSIS AND TROUBLESHOOTING WITHOUT ERROR CODE (CONT)
Field Maintenance
Restricted
Possible causes
Compressor
Refrigerant
of trouble
stuck
Shortage
Unit will not start
Compressor will not
start however the
fan runs
Compressor and
condenser
(outdoor) fan will
not start
Evaporator (indoor)
fan will not start
Condenser (out­
door) fan will not
start
Unit runs but
shortly stops
Compress or short
cycles due to
overload
High discharge
pressure
Low discharge
pressure
High suction
pressure
Low suction
pressure
Unit runs
continuously but
insufficient cooling
Too cool
Compressor is
noisy
Horizontal louver
can not revolve
Replace
Test method /
Replace the
Leak test
remedy
compressor
restricted
Insufficient
Dry
Dirty
air
Refrigerant
liquid
air
evaporator
through
overcharge
line
filter
coil
evaporator
coil
Change
Clean
the
Check
charged
or
Clean coil
fan
refrigerant
replace
part
volume
Table 13—Field Maintenance (Con't)
Refrigerant Circuit
Air or non-
Dirty or
Short
condensable
High temp.
partially
cycling of
gas in
condensing
blocked
condensing
medium
refrigerant
condenser
air
cycle
Clean
Purge,
Remove
Remove
condenser
evacuate
obstruction
obstruction
or remove
and
in air or
to air flow
obstacle
recharge
water flow
Broken
Insufficient
Expansion
compressor
Insufficient
condensing
valve
internal
compressor
medium
obstructed
parts
Remove
Test
obstruction
Replace
Replace
compressor
in air or
compressor
valve
efficiency
water flow
Expansion
Leaking
Power
valve or
power
installation
capillary
element on
of feeler
tube closed
expansion
bulb
completely
valve
Replace
Replace
Fix feeler
valve
valve
bulb