Lennox 2PGE13 series Installation Instructions Manual page 4

Gas heating / electric cooling package unit
Table of Contents

Advertisement

Roof Curb Installation
If a roof curb is used, follow the manufacturer's
installation
instructions and be sure that all required clearances are
observed (see following Clearances
section).
Roof Curb Assembly
Figure
2
Clearances
All units require certain clearances for proper operation
and service. Refer to Table 1 for the minimum clearances
to combustibles as well as minimum clearances neces-
sary for servicing and proper unit operation.
Minimum
Clearance
Requirements
Front
24"
48"
3"
Rear
0!!
24!!*
3!! _
n
n
Condenser
0"
24"
3"
End
Blower
,
'
0!'
30"
0!!
End
.
.
,
Top
0"
36"
36"
Table 1
Figure 3 shows the minimum clearances to combustibles
required above and below the vent hood. The minimum
clearance in front of the vent hood is 24".
Do not permit overhanging
structures
or shrubs to
obstruct
condenser
air discharge
outlet or vent outlet.
Minimum
Clearance
to Combustibles
Above
and Below
the Vent Hood
Minimum Clearance
Above Vent Hood:
Distance from Top
of Vent Hood to Top
of Unit
Minimum Clearance
Below Vent Hood:
Distance from Bottom
of Vent Hood to Base
of Unit
Figure
3
In the U.S., units may be installed on combustible floors
made from wood or class A, B, or C roof covering material.
In Canada, units may be installed on combustible floors.
Service Access
Access to all serviceable components is provided by four
removable panels: filter compartment, blower compart-
ment, furnace compartment, and top panel.
Combustion Products Discharge
The unit must be positioned such that combustion prod-
ucts discharged at the vent outlet will not result in building
degradation and must be consistent with the National Fuel
Gas Code, Z223.1 or CAN/CGA-B149.1
& .2.
The products of combustion are discharged through a
screened opening in the front mullion. The horizontal vent
system shall terminate at least 4' below, 4' horizontally
from, or 1' above any door, window, or gravity air inlet into
the building. The vent system shall terminate at least 3'
above any forced air inlet located within 10'.
The unit shall be installed in a manner such that snow
accumulation will not restrict the flow of flue products.
Minimum horizontal clearance of 4' from electric meters,
gas meters, regulator, and relief equipment is required.
In addition to the above requirements, consideration
must
be given to prevent unwanted ice buildup from the vent
condensate. The vent should not be located on the side of
a building where the prevailing winter winds could trap the
moisture, causing it to freeze on the walls or on overhangs
Page 4