Condensation drain predisposition

For heat pump appliances, a condensation drain pipe (Ø10
mm, internal, not supplied) must connect the unit to the
pipe on the top part of the appliance.
A solenoid valve will start the flow of the condensation from
the internal collection tray when the maximum level has
been reached. For cooling only appliances, said pipe must
be connected if the appliance is going to be used with low
external temperatures (below 23°C). The drainage occurs by
gravity. For this reason, it is essential for the line to have at
least a 3% minimum slope in every point. The pipe to be used
can be rigid or flexible with a minimum inner diameter of
10 mm. If the line flows into a sewer system, it is necessary
to add a siphon before placing the pipe into the main drain.
Said siphon must be placed at least 300 mm under the
mouth of the appliance.

Assembling air ducts and external shutters

Once the holes have been made, place the supplied plastic
sheets inside them.
Roll up the sheet and insert it in the hole, checking that the
A junction line is aiming upwards.
Use a cutter to remove any excess pipe.
To place the external grids, proceed as follows:
-
connect the chains to the ends of the springs;
-
fold the external shutters;
-
insert your arm in the hole to push the shutter outside
while holding the ends of the chains with the other hand
to prevent them from falling down;
-
open the shutter inside the hole;
-
rotate the shutter to bring the flap in the vertical C
position and check that the closing mechanism works;
-
pull the chains by tensioning the springs;
-
use a bolt cutter to remove any excess chain.
-
anchor the hook of the chain to wall B.
10
Soloclim
If the line flows into a container (e.g. a tank), do not
close the container hermetically and avoid immersing
the draining pipe into the water.
The hole for the condensation pipe must always lean
towards the outside.
The exact position in which to place the pipe mouth is
indicated on the template.
Check that the expelled water does not cause any
damage or problems to people or objects. During winter,
this water may create sheets of ice outside.
When connecting the condensation drain, be careful not
to squeeze the rubber duct.
It is possible to empty the collection tray using the
safety drain at the base of the appliance if necessary.
1
Safety drain to empty tray
2
Condensation drain duct
Use only the supplied grids or grids with the same
characteristics.
The shutters must be positioned with the flap in vertical.
The shutters are different. Should be distinguished from
that position on the recovery from the one place on the
delivery, according to the opening direction of the fins.